148
Eaton Power Xpert 9395C UPS Installation and Operation Manual 164000821—Rev 06
•
Determine if the battery is inadvertently grounded. If it is, remove the source of the ground. Contact with
any part of a grounded battery can result in electrical shock. The likelihood of such shock is reduced if such
grounds are removed during installation and maintenance.
•
When replacing batteries, use the same number of sealed, lead-acid batteries.
•
Proper disposal of batteries is required. Refer to your local codes for disposal requirements.
•
Do not dispose of batteries in a fire. Batteries may explode when exposed to flame.
•
Do not open or mutilate batteries. Released electrolyte is harmful to the skin and eyes. It may be toxic
99..22
P
Peerrffoorrm
miinngg P
Prreevveennttiivvee M
Maaiinntteennaannccee
The UPS system requires very little preventive maintenance. However, the system should be inspected
periodically to verify that the units are operating normally and that the batteries are in good condition.
99..22..11
D
DA
AIILLYY M
Maaiinntteennaannccee
Perform the following steps daily:
1.
Check the area surrounding the UPS system. Ensure the area is not cluttered, allowing free access to the
unit.
2.
Ensure the air intakes (vents on the front door or panels) and the exhaust openings (on top of the PM
section) are not blocked.
3.
Ensure the operating environment is within the parameters specified in paragraph
and
4.
Ensure the UPS is in Normal mode (Normal status indicator is illuminated). If an alarm lamp is illuminated
or the Normal status indicator is not illuminated, contact an Eaton service representative.
99..22..22
M
MO
ON
NTTH
HLLYY M
Maaiinntteennaannccee
Perform the following steps monthly:
1.
Monitor system parameters as described in paragraph
Using the Color Touchscreen Control Panel
2.
Check the UPS air filters (located behind the front panels or door) and wash or replace as necessary. See
and
for filter locations, and
for filter sizes. Contact an Eaton service
representative for replacement filters.
To remove and replace the filters:
Table 31. UPS Filter Sizes
Filter Location
Size
Part Number
Bottom Left ISBM Section Air Filters
(Continuous Static Switch)
20” X 11.9” X 0.5”
151201043-001
Bottom Right ISBM Section Air Filters
(Continuous Static Switch)
20” X 11.9” X 0.5”
151201043-001
Middle Right ISBM Section Air Filter
(Continuous Static Switch)
20” X 6.3” X 0.5”
151902001
ISBM Section Air Filters
60.6” X 20” X 0.25”
P-151000035