14
Eaton Power Xpert 9395C UPS Installation and Operation Manual 164000821—Rev 06
NOTE
If Eaton battery cabinets are located in the same room as the UPS, the battery cabinet
environmental requirements supercede the UPS requirements. Operating temperatures
above the recommended range will result in decreased battery life and performance,
and will reduce or void the battery warranty. Refer to Eaton’s
Terms and Conditions of
Sale with Battery Replacement Coverage
and the
Battery Replacement Price Book
for
more information. These documents can be found at www.eaton.com/powerquality or
contact an Eaton service representative to obtain copies.
The UPS ventilation requirements are shown in
.
Table 4. 480V Air Conditioning or Ventilation Requirements During Full Load Operation
Model
Rating
Input/Output
Voltage
Heat Rejection
kW (BTU/hr)
Ventilation Required for Cooling Air Exhaust
Eaton 9395C
1000 kW
1000 kVA
480/480
37.3 (128)
Approximately 4250 liter/sec (9000 CFM)
1000 kW
1100 kVA
480/480
37.3 (128)
1100 kW
1100 kVA
480/480
342.3 (144)
Figure 2. UPS Cabinet Dimensions – (Front View)
Dimensions are in millimeters [inches].
1964
[77.3]
3731
[146.9]