Eaton Power Xpert 9395C UPS Installation and Operation Manual 164000821—Rev 06
Table 8. External Power Cable Terminations
Terminal Function
Terminal
Function
Bus Landings
(using both sides of bus)
Tightening Torque
Nm (lb ft)
Bolt Size
AC Input to UPS
Rectifier
E1
Phase A
6 – 2 bolt mounting
76 (56)
M12
E2
Phase B
6 – 2 bolt mounting
76 (56)
M12
E2
Phase C
6 – 2 bolt mounting
76 (56)
M12
AC Input to Bypass
E6
Phase A
6 – 2 bolt mounting
76 (56)
M12
E7
Phase B
6 – 2 bolt mounting
76 (56)
M12
E8
Phase C
6 – 2 bolt mounting
76 (56)
M12
AC Output to Critical
Load
E9
Phase A
6 – 2 bolt mounting
76 (56)
M12
E10
Phase B
6 – 2 bolt mounting
76 (56)
M12
E11
Phase C
6 – 2 bolt mounting
76 (56)
M12
DC Input from
Battery or Battery
Disconnect to UPS
E4
Battery (+)
16 – 2 bolt mounting
76 (56)
M12
E5
Battery (-)
16 – 2 bolt mounting
76 (56)
M12
NOTE Customer ground, sized in accordance with NEC Table 250.122, can be run in any conduit listed in
Table 9. Supplied External Wiring Terminal Hardware Kit
Part
Size
Quantity
Terminals Used On
Eaton Part Number
Bolt, Grade 5
M10 x 40 mm
30
Ground and Neutral
180190078-088
Bolt, Grade 5
M12 x 50 mm
86
Rectifier Input, Bypass Input, Battery
Input, and Output
180190078-115
Flat Washer
M12
52
Rectifier Input, Bypass Input, Battery
Input, and Output
180500036-120
Conical
Washer
M12
26
Rectifier Input, Bypass Input, Battery
Input, and Output
180500037-120
Nut
M12
26
Rectifier Input, Bypass Input, Battery
Input, and Output
180200001-07
Table 10. Recommended Installation Parts and Tools (Not Supplied by Eaton)
Part
Size
Quantity
Manufacturer
Part Number
Notes
Long Barrel 2-Hole Lug
2/0 AWG
Thomas & Betts
54862BE
Copper wire
only
3/0 AWG
Thomas & Betts
54864BE
4/0 AWG
Thomas & Betts
54866BE
250 MCM
As required
Thomas & Betts
54868BE
300 MCM
Thomas & Betts
54870BE