Eaton Power Xpert 9395C UPS Installation and Operation Manual 164000821—Rev 06
63
Figure 35. Typical Battery Interface Connection
Battery
Breaker or
Disconnect
TB1
Battery Aux
Battery Aux Common
48 Vdc Battery Shunt Trip +
48 Vdc Battery Shunt Trip –
UPS
ST
5
6
7
8
NOTE
Battery Aux and DC Shunt Trip wiring should be a minimum of 18
AWG.
44..77..33
X
X--S
Slloott C
Coonnnneeccttiioonnss
NOTE
LAN and telephone drops for use with X-Slot cards must be provided by the customer.
NOTE
When installing external wiring to X-Slot cards, conduit must be installed to the UPS
cabinet. When installing internal wiring to X-Slot terminals, route the wiring through the
internal opening in the X-Slot communication bay.
For installation and setup of an X-Slot card, contact an Eaton service representative (see
).
To install wiring to connections:
1.
If not already installed, install the LAN drops.
2.
Unfasten the front door latch and swing the door open (see
).
3.
Remove the right interface entry conduit landing plate to drill or punch holes (see
4.
Reinstall the interface entry plate and install the conduit.
5.
Route and install the LAN and other cables to the appropriate X-Slot cards. See
and
for
X-Slot communication bay locations.
6.
Close the door and secure the latch.
7.
Refer to the manual supplied with the X-Slot card for operator instructions
Summary of Contents for Power Xpert 9395C