78
Eaton Power Xpert 9395C UPS Installation and Operation Manual 164000821—Rev 06
3.
Securely mount the SCM II at the desired location. See
for mounting hole locations.
NOTE
When installing signal wiring for CAN card J3 terminals, conduit must be installed
between the device and the UPS cabinet.
4.
Remove the ISBM cabinet top right interface conduit landing plate to drill or punch conduit holes (see
).
5.
Reinstall the conduit landing plate.
6.
Install conduit between the UPS and SCM II. See
for SCM II knockout hole location.
7.
Install wiring between the UPS and SCM II. See
and
for the Powerware Hot Sync CAN
Bridge Card terminal location and wiring information, and
,
, and
for the SCM II
terminal location and wiring information.
NOTE
120 Vac for the RMP II should be supplied from the critical bus by facility planners or the
customer.
8.
Install 120 Vac power wiring from the critical bus to the SCM II. See
,
, and
for
the terminal location and wiring information
NOTE
Setup of the Powerware Hot Sync CAN Bridge Card must be performed by an
authorized Eaton Customer Service Engineer. Contact an Eaton service representative
to schedule a date.
9.
Close the front door and secure the latch.
10. Restart the UPS. See
for startup instructions.
Figure 45. Remote Monitor Panel II and Remote Monitor Panel II Terminal Locations
Terminal TB1
Signal Connections
from the UPS
Ground
Terminal
Terminal TB3
120 Vac Power