INSTALLING OPTIONS AND ACCESSORIES
Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual
S
P-164000500 Rev 4
www.eaton.com/powerquality
5-2
5.1
Installing an Optional Powerware Hot Sync CAN Bridge Card
As an option, a Powerware Hot Sync Controller Area Network (CAN) Bridge Card,
shown in Figure 5‐1, can be installed to provide connectivity for operational mode
control of a parallel system. In addition, this card can be used to connect optional
system monitoring devices, such as a Remote Monitor Panel II, a Relay Interface
Module II, or a Supervisory Contact Module II to the UPS.
Plug-in Terminal
Block J3
Figure 5‐1. Powerware Hot Sync CAN Bridge Card
NOTE
Only one Powerware Hot Sync CAN Bridge Card can be installed in the UPS. Multiple CAN cards are
not supported and will cause system conflicts.
To install the card:
1.
Verify the UPS system is turned off and all power sources are removed. See
Chapter 7, “UPS Operating Instructions,” for shutdown instructions.
2.
Unfasten the front door latch and swing the door open (see Figure 4‐1).
3.
Install the Powerware Hot Sync CAN Bridge Card into an open X-Slot
communication bay on the front of the UPS. See Figure 4‐21 and Figure 4‐27 for
X-Slot communication bay locations.
To locate the appropriate terminals on the Powerware Hot Sync CAN Bridge
Card, see Figure 5‐2 and Table 5‐1.