124
9395P 250 kVA / 275 kVA / 300 kVA
User’s and Installation Guide
9.
On the UPM Control Command screen, select
UPM GO TO ONLINE
.
10.
Press the
SELECT
pushbutton on the UPM Command menu bar.
The UPM transfers to Online mode. The UPM status indicates ONLINE.
7.5.22 UPS and Critical Load Shutdown
To perform maintenance or service on the critical load, shut down power to the load:
1.
Turn off all equipment that is being powered by the UPS.
2.
Perform the LOAD OFF procedure in paragraph 7.5.24.
The input, output, battery, and bypass backfeed contactors open, and the power module
is turned off.
3.
If the UPS contains input breaker CB1, open the UPS input breaker CB1.
4.
Open the UPS input and bypass feeder circuit breakers.
7.5.23
Charger Control
To turn the battery charger on:
1.
Press the
CONTROLS
pushbutton on the main menu bar. The System Status screen is displayed.
2.
On the System Status screen, select the
CHARGER
command.
3.
Press the
CONTROLS
pushbutton on the System Status menu bar. The Charger Control Command
screen is displayed.
4.
On the Charger Control Command screen, select
CHARGER ON
.
5.
Press the
SELECT
pushbutton on the Charger Command menu bar.
To turn the battery charger off:
1.
Press the
CONTROLS
pushbutton on the main menu bar. The System Status screen is displayed.
2.
On the System Status screen, select the
CHARGER
command.
3.
Press the
CONTROLS
pushbutton on the System Status menu bar. The Charger Control Command
screen is displayed.
4.
On the Charger Control Command screen, select
CHARGER OFF
.
5.
Press the
SELECT
pushbutton on the Charger Command menu bar.
WARNING
Power is present inside the UPS cabinet until the upstream input feeder circuit breaker is opened.
7.
5
.24
Using the UPS LOAD OFF Pushbutton or Command
A UPS Load Off is initiated by the
LOAD OFF
pushbutton from the main menu bar, the Load Off command
on the UPS Control Command screen, or Load Off command on the Bypass Control Command screen.
The UPS
LOAD OFF
controls the UPS output by powering down the UPS and de
‐
energizing the critical load.
The UPS (including Bypass) remains off until restarted.
To use the
LOAD OFF
pushbutton: