24
9395P 250 kVA / 275 kVA / 300 kVA
User’s and Installation Guide
4 UPS system installation
4.1 Preliminary installation information
WARNING
Installation should be performed only by qualified personnel.
Refer to the following while installing the UPS system:
•
Chapter 3: “UPS installation plan and unpacking” for cabinet dimensions, equipment weight,
wiring and terminal data, and installation notes.
•
Do not tilt the cabinet more than ±10° during installation.
•
The landing plates can be removed to add cable entry holes as required. Plate material is 16 gauge
steel (1.5 mm/0.06” thick).
•
If perforated floor tiles are required for ventilation, place them in front of the UPS.
4.2 Unloading the UPS cabinet from the pallet and
mechanical installation
The UPS cabinet is bolted to a wooden pallet supported by wood skids. To remove the pallet and
mechanically install the UPS, perform the following procedure:
WARNING
The UPS cabinet is heavy. See Table 3-1 for weight of cabinets. If unloading instructions are
not closely followed, the cabinet may cause serious injury and equipment damage.
Do not tilt cabinets more than 10° from vertical.
Lift the cabinet only with a forklift or damage may occur.
CAUTION
•
Do not tilt cabinets more than 10° from vertical.
•
Lift the cabinet only with a forklift or damage may occur.
•
•
•