47
9395P 250 kVA / 275 kVA / 300 kVA
User’s and Installation Guide
4.8 Installing a
R
EPO switch
NOTE
Before installing a REPO switch, verify that the UPS was installed according to the instructions
in paragraphs 4.2 through 4.7.
When installing the REPO switch, you must install conduit between the device and the UPS
cabinet for wiring the switch.
Remove the UPS cabinet interface entry conduit landing plates to drill or punch holes (see
Figure
4‐4).
The REPO switch must be a normally-open or normally-closed
latching‐type
switch not tied
into any other circuits.
This procedure is intended to be used for the installation of the Eaton-supplied REPO switch. If
installing another manufacturer's switch, use this procedure only as a guide.
The REPO switch wiring must be in accordance with NEC Article 725 Class 2 requirements.
A latching-type Remote Emergency Power-off (REPO) switch can be used in an emergency to shut
down the U
PS
and remove power to the critical load from a location away from where the UPS is
installed. Figure 4
-
20 shows a REPO switch.
Figure 4-
20
. REPO switch
•
•
•
•
•
•
To Install a REPO switch:
1.
Verify the UPS system is turned off and all power sources are removed. See Chapter 7, “UPS
Operating Instructions,” for shutdown instructions.
2.
Securely mount the REPO switch. Recommended locations include operator's consoles or near exit
doors. See Figure 3
‐
7 for enclosure dimensions and wiring knockouts.
3.
Unfasten the front door latch and swing the door open (see Figure 4
‐
2).
4.
Remove the door. Remove the retaining screw located inside the door at the bottom hinge pivot point,
then lift the door off. Retain the hardware for later use.
5.
If installing interface wiring through the left interface entry conduit landing, proceed to Step 6;
otherwise, proceed to Step 8.
REPO Switch (Front View)
Contact Block (Back View, Faceplate Removed)
Summary of Contents for Power Xpert 9395P 250 kVA
Page 1: ...User s and Installation Guide Power Xpert 9395P UPS 250 kVA 275 kVA 300 kVA...
Page 2: ......
Page 3: ...Power Xpert 9395P UPS 250 kVA 275 kVA 300 kVA User s and Installation Guide...
Page 168: ......
Page 169: ......
Page 170: ...614 01919 00...