45
9395P 250 kVA / 275 kVA / 300 kVA
User’s and Installation Guide
17.
Reinstall the small top internal safety shield panel and secure with the cabinet mounted screws.
18.
If wiring X-Slot connections, proceed to paragraph 4.7.3; otherwise, proceed to Step 19.
19.
Reinstall the front door removed in Step 3 and secure with the retained hardware.
20.
Close the door and secure the latch.
21.
If removed, reinstall the safety shield panel removed in Step 6. Secure with the retained hardware.
22.
If removed, reinstall the left front panel removed in Step 5 and secure with the retained hardware.
Battery
Breaker or
Disconnect
TB1
Battery Aux
Battery Aux Common
48 Vdc Battery Shunt Trip +
48 Vdc Battery Shunt Trip –
UPS
ST
5
6
7
8
Figure 4‐17. Typical Battery Interface Connection
UPM 1
Battery
Breaker or
Disconnect
TB1
UPS
ST
UPM 4
Battery
Breaker or
Disconnect
ST
48 Vdc
Battery Aux
Battery Aux Return
48 Vdc Battery Shunt Trip
48 Vdc Battery Shunt Trip
5
6
7
8
Figure 4‐18. Typical Battery Interface Connection – Separate Battery System
NOTE
Battery Aux and DC Shunt Trip wiring should be a minimum of
18 AWG
.
NOTE
Battery Aux and DC Shunt Trip wiring should be a minimum of
18 AWG
.