Table 50. UPS Output
UPS Output Capacity
100% rated current
Output Voltage Regulation
±1.5% (10% to 100% load)
Output Voltage
(N/–3%)
600 Vac nominal, adjustable from 582 Vac to 618 Vac
575 Vac nominal, adjustable from 558 Vac to 592 Vac
480 Vac nominal, adjustable from 466 Vac to 494 Vac
400 Vac nominal, adjustable from 388 Vac to 412 Vac
380 Vac nominal, adjustable from 369 Vac to 391 Vac
Output Voltage Harmonic Content
1.5% maximum THD (linear load)
5% maximum THD (nonlinear load)
Output Current
See
or
for 600V One/Two/Three UPM models.
See
or
for 575V One/Two/Three UPM models.
See
or
for 480V One/Two/Three UPM models.
See
or
for 415V One/Two/Three UPM models.
See
or
for 400V One/Two/Three UPM models.
See
or
for 380V One/Two/Three UPM models.
Output Voltage Balance
2.5% for 100% maximum load imbalance (linear load)
Output Voltage Phase Displacement
±4° for 100% maximum load imbalance (linear load)
Output Transients
Meets Class 1 IEC 62040-3 (10% to 100% load)
Frequency Regulation
±0.1 Hz free running
Synchronous to Bypass
+10% to -10%
Frequency Slew Rate
.7 Hz per second maximum
Load Compatibility
0.9 pF Leading
0.8 pF Lagging
Overload Capability
110% for 10 minutes
125% for 120 seconds
150% for 15 seconds
NOTE
The 125% and 150% overloads are based on the non-derated hardware capability of the
UPS.