Eaton
®
Power Xpert
®
9395P-600 (300V-600V) Installation and Operation Manual 164000710—Rev 07
69
44..33
M
Meecchhaanniiccaallllyy JJooiinniinngg tthhee S
Seeccttiioonnss ((660000V
V M
Mooddeellss O
Onnllyy))
NOTE
The following procedure permits the UPS sections to be installed in a location where
there is limited space to slide the sections together from the sides.
NOTE
For the following steps, verify that the forklift or pallet jack is rated to handle the weight
of the section (see
for cabinet weight).
1.
Using a forklift, move the UPM section to the final installed location.
2.
Remove one top screw and two bottom screws securing the UPM section wireway panel (see
Lift the panel straight up to remove it from the panel hanger brackets at the top of the cabinet.
3.
Remove the screws securing the top and bottom internal safety shield panels and remove the panels.
Retain the hardware for later use.
4.
Remove the screws securing the corner channel and remove the channel (see
). Retain the
hardware for later use.
Figure 21. Section Joining
Left Top Panel
Wireway Panel
Left Middle Panel
Corner Channel
UPM Section
Interior Left Side Panel