94
Eaton
®
Power Xpert
®
9395P-600 (300V-600V) Installation and Operation Manual 164000710—Rev 07
Figure 39. Typical Battery Interface Connection – Common Battery System
Battery
Disconnect
TB1
Battery Aux
Battery Aux Common
48 Vdc Battery Shunt Trip +
48 Vdc Battery Shunt Trip –
UPS
ST
5
6
7
8
NOTE
Battery aux and DC shunt trip wiring should be a minimum of 18 AWG.
48 Vdc
Figure 40. Typical Battery Interface Connection – Separate Battery System
48 Vdc Battery Shunt Trip +
48 Vdc Battery Shunt Trip –
TB1
UPS
UPM 1
Battery
Disconnect
ST
FI-UPM
Battery
Disconnect
ST
48 Vdc
Battery Aux
Battery Aux Return
5
6
7
8
ST
UPM 2
Battery
Disconnect
44..99..33
X
X--S
Slloott C
Coonnnneeccttiioonnss
NOTE
LAN and telephone drops for use with X-Slot cards must be provided by the customer.
NOTE
When installing external wiring to X-Slot cards, conduit must be installed to the UPS
cabinet. When installing internal wiring to X-Slot terminals, route the wiring through the
internal opening in the X-Slot communication bay.
For installation and setup of an X-Slot card, contact an Eaton service representative (see paragraph Getting Help
).
To install wiring to connections:
1.
If not already installed, install the LAN drops.
Summary of Contents for Power Xpert 9395P-600/600