background image

124

Eaton

®

Power Xpert

®

9395P-600 (300V-600V) Installation and Operation Manual 164000710—Rev 07

The emergency bypass consists of a continuous static switch, and a backfeed protection contactor K5. The
bypass breaker (if installed) is located in parallel with the static switch. The backfeed protection contactor is
located in series with the static switch. The static switch is armed and ready during normal operation.

On a UPS configured as an Input Output Module (IOM), bypass circuitry is not installed. This configuration is
primarily used in multiple UPS parallel systems that do not need a bypass for each UPS and use a separate
System Bypass Module (SBM) to provide system bypass capabilities.

66..22

S

Siinnggllee U

UP

PS

S

A single UPS operates independently to support an applied load from the inverter, providing conditioned and
uninterruptible AC power to the critical load from the output of the module. During an outage, the inverter
continues to operate, supporting power to the load from the battery supply. If the unit requires service, applied
loads are transferred to the internal bypass, continuous-duty static switch either automatically or manually.
With the exception of a battery cabinet, no other cabinets or equipment are required for the single UPS to
successfully support its applied loads.

66..22..11

M

Mooddeess

The Eaton 9395P-600 UPS supports a critical load in five different modes of operation:

NOTE

The Variable Module Management System and Energy Saver System modes are
mutually exclusive.

In Online mode, the critical load is supplied by the inverter, which derives its power from rectified utility AC
power. In this mode, the battery charger also provides charging current for the battery, if needed.

In Energy Saver System (ESS) mode, commercial AC power is supplied directly to the critical load through
the continuous static switch and transfers automatically to Online mode if an abnormal condition is
detected.

In Variable Module Management System (VMMS) mode, the UPS operates as a traditional double-
conversion UPS, but selectively shifts the load to fewer UPMs to increase the efficiency of the UPS.

In Bypass mode, the critical load is directly supported by utility power.

In Battery mode, the battery provides DC power, which maintains inverter operation. The battery supports
the critical load.

The following paragraphs describe the differences in the UPS operating modes, using block diagrams to show
the power flow during each mode of operation.

66..22..22

O

Onnlliinnee M

Mooddee

Figure 62

shows the path of electrical power through the UPS system when the UPS is operating in Online

mode.

During normal UPS system operation, power for the system is derived from a utility input source through the
rectifier input contactor K1. The front panel displays "Online" indicating the incoming power is within voltage
and frequency acceptance windows. Three-phase AC input power is converted to DC using IGBT devices to
produce a regulated DC voltage to the inverter. When contactor K2 is closed the battery is charged directly
from the regulated rectifier output through a buck DC converter.

The battery converter derives its input from the regulated DC output of the rectifier and provides either a
boosted or bucked regulated DC voltage charge current to the battery. The battery is always connected to the
UPS and ready to support the inverter should the utility input become unavailable.

The inverter produces a three-phase AC output to a customer's load without the use of a transformer. The
inverter derives regulated DC from the rectifier and uses IGBT devices and pulse-width modulation (PWM) to
produce a regulated and filtered AC output. The AC output of the inverter is delivered to the system output
through the output contactor K3.

Understanding UPS Operation

Summary of Contents for Power Xpert 9395P-600/600

Page 1: ...For use with 380V 400V 415V and 480V Single UPM 200 600 kVA Two UPM 400 550 kVA and Plus 1 400 600 kVA UPS Models Also for use with 600V Single UPM 200 275 kVA Two UPM 300 550 kVA and Plus 1 600 kW 5...

Page 2: ...INSTRUCTIONS This manual contains important instructions that you should follow during installation and maintenance of the UPS Please read all instructions before operating the equipment and save this...

Page 3: ...m a host of threats including power outages surges lighting strikes and enable you to monitor and control your power infrastructure We trust that your Eaton 9395 Uninterruptible Power Supply system wi...

Page 4: ...e license to use the Firmware in conjunction with the operation of the product to which the Firmware pertains or other products as described by Eaton in the Documentation Licensee does not acquire any...

Page 5: ...CT IS AT LICENSEE S SOLE RISK 5 0 GENERAL PROVISIONS 5 1 Update Policy Eaton may from time to time but has no obligation to create Updates of the Firmware or components thereof 5 2 Limitation on Liabi...

Page 6: ...nctions Programs Pages Programs aspx or to any national of any such country wherever located who intends to transmit or transport the Firmware back to such country ii to any end user who Licensee know...

Page 7: ...nfidential aspects of the Firmware shall not be disclosed to third parties without the prior written consent of Eaton Accordingly Eaton will be entitled to preliminary and permanent injunctive and oth...

Page 8: ......

Page 9: ...s Static Switch 8 1 4 8 Inherent Redundancy 8 1 4 9 Energy Saver and High Alert Modes 8 1 4 10 Variable Module Management System and High Alert Modes 8 1 4 11 Monitoring and Communication 9 1 5 Batter...

Page 10: ...wer Wiring 84 4 9 Installing Interface Connections 86 4 9 1 TB1 TB2 and TB3 Connections Other than TB1 Battery Interface Connections 87 4 9 2 TB1 Battery Interface Connections 93 4 9 3 X Slot Connecti...

Page 11: ...tons 157 7 3 4 Power Maps Screen Online Mode 158 7 3 5 Power Maps Screen Bypass Mode 160 7 3 6 Command Confirmation Pop Up 161 7 3 7 Meters Summary Screen 161 7 3 8 Input Meters Screen 162 7 3 9 Input...

Page 12: ...PredictPulse 192 8 3 Power Management Software 193 8 4 Building Alarm Monitoring 193 8 5 General Purpose Relay Contact 193 8 6 Remote Monitor Panel II 193 8 7 Relay Interface Module II 196 8 8 Supervi...

Page 13: ...ation Plus 1 FI UPM Dimensions 34 Figure 17 Side View Dimensions and Center of Gravity Measurements 35 Figure 18 Two UPM Configuration as Shipped on Pallet 380V 400V 415V and 480V 64 Figure 19 Removin...

Page 14: ...60 Supervisory Contact Module II Dimensions 122 Figure 61 Main Elements of the UPS System 123 Figure 62 Path of Current Through the UPS in Online Mode 125 Figure 63 Path of Current Through the UPS in...

Page 15: ...een from Home Screen 160 Figure 91 Consumption Screen from Home Screen 160 Figure 92 Bypass Screen 161 Figure 93 Typical Command Confirmation Screen Charger Off 161 Figure 94 Meters Summary Screen 162...

Page 16: ...e Map Screen 177 Figure 121 System Overview Screen 177 Figure 122 REPO Operation 180 Figure 123 Optional X Slot Cards 191 Figure 124 Remote Monitor Panel II 194 Figure 125 Relay Interface Module II 19...

Page 17: ...g Recommendations for the One Two Three UPM Common Battery 43 Table 14 415V Input Output Ratings and External Wiring Recommendations for the One Two Three UPM Separate Battery 44 Table 15 400V Input O...

Page 18: ...Wiring Terminations 111 Table 38 Pull Chain Wiring Terminations with MOBs 113 Table 39 RMP II RIM II or SCM II Wiring Terminations 115 Table 40 J1 through J4 Interface Connectors 117 Table 41 Oneline...

Page 19: ...s see Figure 1 two optional configurations with a field installed UPM FI UPM added to the left of a standard configuration see Figure 3 NOTE The FI UPM is not supplied as standard but is available as...

Page 20: ...ion Manual 164000710 Rev 07 Figure 1 Standard Single UPM and Two UPM UPS Configurations all except the 600V model ISBM UPM UPM ISBM UPM Standard ISBM and 1 x UPM 380V 400V 415V and 480V models Standar...

Page 21: ...stallation and Operation Manual 164000710 Rev 07 3 Figure 2 600V Single UPM and Two UPM UPS Configurations 600V model only 600V ISBM UPM 600V ISBM UPM 600V ISBM and 1 x UPM 600V models only 600V ISBM...

Page 22: ...figuration has three sections an ISBM section configured either as an integrated system bypass module ISBM or an input output module IOM rated for a maximum of 900 kVA a UPM section with two UPMs l on...

Page 23: ...n and 1 x UPM Section Upgraded with Plus 1 Field Installed FI UPM 600V only 600V ISBM Section and 2 x UPM Section Upgraded with Plus 1 Field Installed FI UPM 600V only 600V ISBM Section and 1 x UPM Se...

Page 24: ...ations may limit the number of inputs available The UPS uses these inputs to monitor the building alarms in addition to the UPS status See Chapter 8 Communication for additional information Alarm Cont...

Page 25: ...f jumpers and bus bar extensions for each phase and the hardware required for installation Refer to the Eaton Power Xpert 9395 9395P UPS 1000 1200 kVA Single Feed Kit Installation Instructions P 16400...

Page 26: ...critical bus and instantly and seamlessly transitions to double conversion mode inverter online if a commercial electrical power brownout blackout overvoltage undervoltage or out of tolerance frequenc...

Page 27: ...dashboard and smartphone mobile app Apple and Android giving subscribers insights about past and current performance a list of all active alarms and asset management data i e battery date codes last a...

Page 28: ...ing the procedure Perform only those procedures that apply to the UPS system being installed or operated 1 1 7 7 C Co on nv ve en nt tiio on ns s U Us se ed d iin n T Th hiis s M Ma an nu ua all This...

Page 29: ...n contact your local recycling reuse or hazardous waste center This symbol indicates that you should not discard waste electrical or electronic equipment WEEE in the trash For proper disposal contact...

Page 30: ...800 843 9433 or 1 919 870 3028 Canada 1 800 461 9166 ext 260 All other countries Call your local service representative Please use the following e mail address for manual comments suggestions or to re...

Page 31: ...nals may carry live voltage even when the UPS is disconnected from an AC source To reduce the risk of fire or electric shock install this UPS in a temperature and humidity controlled indoor environmen...

Page 32: ...onctionnement du produit Lors de la v rification du fonctionnement de l UPS ne pas enlever la mise la terre si des charges y sont raccord es Ne pas ouvrir ni ab mer les batteries L lectrolyte qu elles...

Page 33: ...Garder les portes de l onduleur ferm es et les panneaux avant en place pour garantir une circulation ad quate de l air de refroidissement et pour prot ger le personnel des tensions dangereuses dans l...

Page 34: ...rer compl tement les fourches dans les passages de fourche de la base NE PAS ins rer partiellement les fourches dans les passages pour d placer l armoire Il est possible d ins rer partiellement les fo...

Page 35: ...Site and Chapter 4 Installation to create a logical plan for installing the system 3 3 2 2 P Pr re ep pa ar riin ng g t th he e S Siit te e For the UPS system to operate at peak efficiency the instal...

Page 36: ...create issues One is the creation of microclimates which are persistent variations of temperature and or RH within a single room for example one side of the room is always cooler than the other side n...

Page 37: ...ton 9395P 600 250 Eaton 9395P 600 225 Eaton 9395P 600 200 ISBM CSS 1 UPM 915 2017 865 1904 NOTE CSS Continuous Static Switch NOTE Table 4 describes power ratings of each model The UPS cabinets use for...

Page 38: ...0 kVA 500 kVA 600 600 27 6 94 3 Eaton 9395P 600 450 CSS or IOM 450 kVA 450 kVA 600 600 24 9 84 9 Eaton 9395P 600 400 CSS or IOM 400 kVA 400 kVA 600 600 22 1 75 5 Eaton 9395P 600 300 CSS or IOM 300 kVA...

Page 39: ...Required for Cooling Air Exhaust Eaton 9395P 600 550 CSS or IOM 550 kVA 550 kVA 415 415 400 400 380 380 22 7 77 42 Approximately 3050 liter sec 6500 CFM Eaton 9395P 600 500 CSS or IOM 500 kVA 500 kVA...

Page 40: ...Center of Gravity measurements that apply for all configurations Single UPM ISBM and 1 x UPM section shipped joined on a single pallet See Figure 5 and Figure 6 Single UPM PLUS 1 UPM ISBM and 1 x UPM...

Page 41: ...164000710 Rev 07 23 Figure 5 Standard Single UPM Configuration Dimensions Front View 1 x UPM 542 9 21 4 ISBM 795 0 31 3 1337 9 52 7 1880 74 0 Dimensions are in millimeters inches Standard ISBM and 1 x...

Page 42: ...00710 Rev 07 Figure 6 Standard Single UPM Configuration Center of Gravity Dimensions are in millimeters inches Front View Standard ISBM and 1 x UPM 380V 400V 415V and 480V models Ventilation Intake 1...

Page 43: ...ngle UPM Configuration Plus 1 FI UPM Dimensions Dimensions are in millimeters inches Front View ISBM 795 0 31 3 1 x UPM 542 9 21 4 FI UPM 735 9 29 0 Standard ISBM and 1 x UPM with 1 Field Installed UP...

Page 44: ...e UPM Configuration Plus 1 FI UPM Center of Gravity Front View 1 x UPM 542 9 21 4 ISBM 795 0 31 3 FI UPM 735 9 29 0 290 0 11 4 1526 0 60 1 Ventilation Intake Standard ISBM and 1 x UPM with 1 Field Ins...

Page 45: ...64000710 Rev 07 27 Figure 9 Standard Two UPM Configuration Dimensions Front View 1880 0 74 0 2 x UPMs 1078 9 42 5 ISBM 795 0 31 3 1873 9 73 8 Dimensions are in millimeters inches Standard ISBM and 2 x...

Page 46: ...0710 Rev 07 Figure 10 Standard Two UPM Configuration Center of Gravity Front View 2 x UPMs 1078 9 42 5 ISBM 795 0 31 3 1085 0 42 7 Ventilation Intake Standard ISBM and 2 x UPMs 380V 400V 415V and 480V...

Page 47: ...Standard Two UPM Configuration Plus 1 FI UPM Dimensions ISBM 795 0 31 3 FI UPM 735 9 29 0 2 x UPMs 1078 9 42 5 Dimensions are in millimeters inches Standard ISBM and 2 UPMs with 1 Field Installed UPM...

Page 48: ...w illustrations of configuration dimensions are provided for each 600V model configuration Figure 17 provides side view illustrations of dimensions and side view Center of Gravity measurements that ap...

Page 49: ...e pallets ready to be joined See Figure 16 NOTE 600V Center of Gravity information will be provided in the next release of this manual Figure 13 600V Single UPM Configuration Dimensions Front View 188...

Page 50: ...14 600V Single UPM Configuration Plus 1 FI UPM Dimensions Front View 1880 0 74 0 ISBM 1873 9 73 8 Dimensions are in millimeters inches 600V ISBM Section with 1 x UPM Section and Upgraded with 1 Field...

Page 51: ...on Manual 164000710 Rev 07 33 Figure 15 600V Two UPM Configuration Dimensions Front View 1880 0 74 0 2 x UPMs 1331 9 52 4 ISBM 1874 73 8 3205 9 126 2 Dimensions are in millimeters inches 600V ISBM Sec...

Page 52: ...16 600V Two UPM Configuration Plus 1 FI UPM Dimensions Front View 1880 0 74 0 2 x UPMs 1331 9 52 4 ISBM 1874 73 8 3941 8 155 2 Dimensions are in millimeters inches 600V ISBM Section with 2 x UPM Sect...

Page 53: ...igure 17 Side View Dimensions and Center of Gravity Measurements Dimensions are in millimeters inches Side View Dimensions 871 5 34 3 1880 0 74 0 NOT INTENDED FOR PERMANENT MOUNTING Side View Center o...

Page 54: ...ires The phases must be symmetrical about ground from a Wye source for proper equipment operation The Eaton 9395P 600 600V and 480V unit is designed for operation on a grounded wye source of supply Th...

Page 55: ...ms See Figure 65 through Figure 75 NOTE Bypass wiring data is not applicable to IOM configurations Battery Conductor Sizing Eaton strongly recommends using the specified DC conductor size and quantity...

Page 56: ...s See Figure 65 through Figure 75 NOTE Bypass wiring data is not applicable to IOM configurations Battery Conductor Sizing Eaton strongly recommends using the specified DC conductor size and quantity...

Page 57: ...ms See Figure 65 through Figure 75 NOTE Bypass wiring data is not applicable to IOM configurations Battery Conductor Sizing Eaton strongly recommends using the specified DC conductor size and quantity...

Page 58: ...re 65 through Figure 75 NOTE Bypass wiring data is not applicable to IOM configurations Battery Conductor Sizing Eaton strongly recommends using the specified DC conductor size and quantity shown abov...

Page 59: ...plicable to IOM configurations Battery Conductor Sizing Eaton strongly recommends using the specified DC conductor size and quantity shown above for optimum system performance and battery run time Bat...

Page 60: ...is not applicable to IOM configurations Battery Conductor Sizing Eaton strongly recommends using the specified DC conductor size and quantity shown above for optimum system performance and battery ru...

Page 61: ...E Bypass wiring data is not applicable to IOM configurations Battery Conductor Sizing Eaton strongly recommends using the specified DC conductor size and quantity shown above for optimum system perfor...

Page 62: ...e 75 NOTE Bypass wiring data is not applicable to IOM configurations Battery Conductor Sizing Eaton strongly recommends using the specified DC conductor size and quantity shown above for optimum syste...

Page 63: ...E Bypass wiring data is not applicable to IOM configurations Battery Conductor Sizing Eaton strongly recommends using the specified DC conductor size and quantity shown above for optimum system perfor...

Page 64: ...75 NOTE Bypass wiring data is not applicable to IOM configurations Battery Conductor Sizing Eaton strongly recommends using the specified DC conductor size and quantity shown above for optimum system...

Page 65: ...E Bypass wiring data is not applicable to IOM configurations Battery Conductor Sizing Eaton strongly recommends using the specified DC conductor size and quantity shown above for optimum system perfor...

Page 66: ...E Bypass wiring data is not applicable to IOM configurations Battery Conductor Sizing Eaton strongly recommends using the specified D C conductor size and quantity shown above for optimum system perfo...

Page 67: ...Bypass E6 Phase A 4 2 bolt mounting 76 56 M12 E7 Phase B 4 2 bolt mounting 76 56 M12 E8 Phase C 4 2 bolt mounting 76 56 M12 AC Output to Critical Load E9 Phase A 4 2 bolt mounting 76 56 M12 E10 Phase...

Page 68: ...30 Ground 180190078 112 Bolt Grade 5 M12 x 50 mm 86 Rectifier Input Bypass Input Battery Input and Output 180190078 115 Flat Washer M12 202 Rectifier Input Bypass Input Battery Input Output and Groun...

Page 69: ...3 4 AC Input to Bypass and Output A B C Ground 4 3 3 Eaton 9395P 600 450 600 Vac AC Input to UPS Rectifier A B C Ground 4 3 3 AC Input to Bypass and Output A B C Ground 4 3 3 Eaton 9395P 600 400 600 V...

Page 70: ...nd Output A B C Ground 4 3 2 or 3 Eaton 9395P 600 400 575 Vac AC Input to UPS Rectifier A B C Ground 4 3 2 or 3 AC Input to Bypass and Output A B C Ground 4 3 2 or 3 Eaton 9395P 600 300 575 Vac AC Inp...

Page 71: ...to UPS Rectifier A B C Ground 4 2 5 3 AC Input to Bypass and Output A B C Ground 4 2 5 3 DC Common Battery Battery Positive Negative Ground 7 4 2 Eaton 9395P 600 300 Eaton 9395P 600 275 Eaton 9395P 6...

Page 72: ...d Output A B C Ground 5 3 3 Eaton 9395P 600 400 415 Vac AC Input to UPS Rectifier A B C Ground 4 3 3 AC Input to Bypass and Output A B C Ground 5 3 3 Eaton 9395P 600 300 415 Vac AC Input to UPS Rectif...

Page 73: ...Output A B C Ground 5 3 3 Eaton 9395P 600 400 400 Vac AC Input to UPS Rectifier A B C Ground 4 3 3 AC Input to Bypass and Output A B C Ground 5 3 3 Eaton 9395P 600 300 400 Vac AC Input to UPS Rectifie...

Page 74: ...Output A B C Ground 5 3 3 Eaton 9395P 600 400 380 Vac AC Input to UPS Rectifier A B C Ground 4 3 3 AC Input to Bypass and Output A B C Ground 5 3 3 Eaton 9395P 600 300 380 Vac AC Input to UPS Rectifi...

Page 75: ...00A 500A 600A 600A 600A 80 450A 450A 600A 700A 700A 700A Eaton 9395P 600 275 100 350A 350A 450A 500A 500A 500A 80 450A 450A 600A 600A 600A 600A Eaton 9395P 600 250 100 300A 300A 400A 450A 450A 450A 80...

Page 76: ...100 300A 350A 400A 450A 450A 500A 80 400A 400A 500A 600A 600A 600A Eaton 9395P 600 275 100 300A 300A 350A 400A 400A 450A 80 350A 350A 450A 500A 500A 600A Eaton 9395P 600 250 100 250A 300A 350A 350A 4...

Page 77: ...ed DC Input Battery Disconnect Ratings 100 Separate Battery UPS Model All Ratings Eaton 9395P 600 600 Eaton 9395P 600 300 800A Eaton 9395P 600 550 Eaton 9395P 600 500 Eaton 9395P 600 400 Eaton 9395P 6...

Page 78: ...he alarm input and common terminal All control wiring and relay and switch contacts are customer supplied and may need to use Class 1 wiring see above The building alarms can be programmed to display...

Page 79: ...not permitted Distributed bypass UPS input wiring size requirements and output wiring size requirements from the UPSs to the tie cabinet or distribution panel are the same as listed in Table 7 to Tab...

Page 80: ...rifier que les fourches du chariot l vateur sont en position horizontale avant de les ins rer dans les passages de fourche NE PAS orienter les pointes de fourche vers le haut Ins rer compl tement les...

Page 81: ...t the pallet on a firm level surface allowing a minimum clearance of 3m 10 ft on each side for removing the cabinet from the pallet NOTE The ISBM and UPM sections are shipped with debris shields cover...

Page 82: ...Eaton Power Xpert 9395P 600 300V 600V Installation and Operation Manual 164000710 Rev 07 Figure 18 Two UPM Configuration as Shipped on Pallet 380V 400V 415V and 480V UPS Installation Plan and Unpacki...

Page 83: ...ed for ventilation place them in front of the UPS 4 4 2 2 U Un nllo oa ad diin ng g t th he e I IS SB BM M w wiit th h U UP PM M S Se ec ct tiio on n f fr ro om m t th he e P Pa alllle et t The ISBM c...

Page 84: ...nal la base de la section de l onduleur lorsque l armoire est soulev e ou d plac e Soulever ou d placer la section de l onduleur en n utilisant que les passages de fourche l avant ou l arri re V rifie...

Page 85: ...olts securing the bracket to the pallet see Figure 19 Remove the left side shipping bracket Figure 19 Removing the ISBM Section Left Side Shipping Bracket Front Door Pallet Shipping Bracket Bolts Ship...

Page 86: ...tion until the cabinet bottom clears the pallet by approximately 3 mm 1 8 5 Pull the pallet from under the UPS cabinet Discard or recycle the pallet in a responsible manner 6 Carefully lower the UPS c...

Page 87: ...section see Table 2 for cabinet weight 1 Using a forklift move the UPM section to the final installed location 2 Remove one top screw and two bottom screws securing the UPM section wireway panel see F...

Page 88: ...posantes du c t droit du module de contournement de syst me int gr ISBM et les faisceaux de c bles reliant les armoires du c t gauche du module d alimentation universel UPM NOTE Clearance between the...

Page 89: ...nt base see Steps 11 and 12 11 Locate the hardware kit packed inside a drawstring bag tied to the left middle panel of the UPM section Locate two flat brackets and screws from the hardware kit Align t...

Page 90: ...d DC input intercabinet power wiring harnesses are supplied coiled and secured in the UPM wireway on the left side of the UPM section see Figure 22 1 Align the ISBM and UPM sections in their final ins...

Page 91: ...cable ground strap in the bottom left front corner of the UPM section The ground braid cable is secured at the factory to the UPM section ground bolt Route the ground braid cable through the wiring ac...

Page 92: ...ing harnesses are supplied coiled inside the protective cage on the right side panel of the ISBM section 1 In the UPM section locate the coiled RJ 45 CAN cable Remove the wire ties securing the cable...

Page 93: ...a battery system proceed to paragraph 4 6 Battery System Installation otherwise proceed to Step 7 7 If installing a tie cabinet or distribution panel for a distributed bypass system proceed to paragra...

Page 94: ...Eaton Power Xpert 9395P 600 300V 600V Installation and Operation Manual 164000710 Rev 07 Figure 26 Pl1 Interface Board Location ISBM Section Right Side Inside View Pl1 Interface Board Front Installati...

Page 95: ...g UPS External and Battery Power Wiring to complete the wiring of the UPS 4 4 7 7 D Diis st tr riib bu ut te ed d B By yp pa as ss s T Tiie e C Ca ab biin ne et t I In ns st ta alllla at tiio on n NOT...

Page 96: ...washers that look similar to flat washers except for a slight conical shape When installing conical washers the top of the dome should be next to the nut and the base of the washer should be against...

Page 97: ...rough Figure 34 for wiring access information and terminal locations Top Access Wiring Remove the top conduit plate from the top of the ISBM section Identify all conduit requirements and mark their lo...

Page 98: ...l or punch conduit holes Bottom Entry Conduit Landing for AC Input and Output and DC Input Remove panel to drill or punch conduit holes BOTTOM VIEW Front Front 4 Locate the external wiring terminal ha...

Page 99: ...ss system proceed to Step 9 otherwise proceed to Step 11 9 Using hardware from the external wiring terminal hardware kit see connect phase A B and C wiring from the output terminals of each UPS unit t...

Page 100: ...ert 9395P 600 300V 600V Installation and Operation Manual 164000710 Rev 07 Figure 31 ISBM Section Power Terminal Locations 380V 400V 415V and 480V Models UPS Input UPS Output Battery Battery Bypass In...

Page 101: ...ower Xpert 9395P 600 300V 600V Installation and Operation Manual 164000710 Rev 07 83 Figure 32 ISBM Section Power Terminal Locations 600V Models UPS Output Battery Battery Bypass Input UPS Input Insta...

Page 102: ...W Wiir riin ng g When sizing the battery system do not exceed the internal battery charger capabilities See Chapter 10 Product Specifications for maximum battery charger currents ATTENTION Lors de l...

Page 103: ...ing from the battery system or disconnect to the ISBM section battery and ground terminals Use both sets of terminals shown in Figure 34 as needed See paragraph 3 2 6 UPS System Power Wiring Preparati...

Page 104: ...nt te er rf fa ac ce e C Co on nn ne ec ct tiio on ns s Hazardous voltages are present near the user interface terminal area if the UPS is not totally disconnected AVERTISSEMENT Des tensions dangereu...

Page 105: ...and the left interface entry conduit landing plates remove the screws securing the top internal safety shield panel and remove the panel Retain the hardware for later use see Figure 35 5 Remove the i...

Page 106: ...88 Eaton Power Xpert 9395P 600 300V 600V Installation and Operation Manual 164000710 Rev 07 Figure 35 ISBM Section Interface Terminal Locations X Slot Communication Bays TB1 TB2 and TB3 Installation...

Page 107: ...mmon Terminal TB2 Name Description 1 Pull Chain Output Backup control for parallel operation 2 Pull Chain Common 3 Alarm Relay NC Output General purpose normally closed NC relay contact 4 Alarm Relay...

Page 108: ...s Input Programmable UPS alarm activated by a remote dry contact closure Default function set for maintenance bypass 10 Building Alarm 5 Return NOTE Return indicates connection to electronics circuit...

Page 109: ...Alarm relay contacts have a maximum current rating of 5A and a switched voltage rating of 30 Vac and 28 Vdc NOTE Alarm relay normally open and normally closed return terminals are separated on the ter...

Page 110: ...for use with either normally open or normally closed contacts All control wiring and relay and switch contacts are customer supplied NOTE The building alarms can be programmed to display the alarm fun...

Page 111: ...nd Figure 35 through Figure 40 NOTE When installing shunt trip and battery aux interface wiring to the UPS interface terminals conduit must be installed between the UPS and battery system 6 Remove the...

Page 112: ...nect ST FI UPM Battery Disconnect ST 48 Vdc Battery Aux Battery Aux Return 5 6 7 8 ST UPM 2 Battery Disconnect 4 4 9 9 3 3 X X S Sllo ot t C Co on nn ne ec ct tiio on ns s NOTE LAN and telephone drops...

Page 113: ...ure 41 for X Slot communication bay locations 6 Close the door and secure the latch 7 Refer to the manual supplied with the X Slot card for operator instructions Figure 41 X Slot Communication Bays X...

Page 114: ...tch If installing another manufacturer s switch use this procedure only as a guide NOTE 6 The REPO switch wiring must be in accordance with NEC Article 725 Class 2 requirements To Install a REPO switc...

Page 115: ...install conduit 8 To locate the appropriate terminals and review the wiring and termination requirements see paragraph 3 2 6 UPS System Power Wiring Preparation Table 33 and Figure 38 9 Route and conn...

Page 116: ...tall wiring from the REPO switch to the trip circuitry of the upstream protective devices A second contact block is provided on the REPO switch for this function see Figure 43 The REPO switch wiring m...

Page 117: ...PO normally open and normally closed return terminals are separated on the terminal board but are electrically in common 1 2 Figure 46 Normally Closed and Normally Open REPO Switch Wiring 3 NO UPS TB1...

Page 118: ...quired to reserve a preferred startup date 4 4 1 13 3 C Co om mp plle et tiin ng g t th he e I In ns st ta alllla at tiio on n C Ch he ec ck klliis st t The final step in installing the UPS system is...

Page 119: ...is properly installed o Air conditioning equipment is installed and operating correctly o The area around the installed UPS system is clean and dust free It is recommended that the UPS be installed o...

Page 120: ...perly routed to the UPS cabinets and to the tie cabinet or distribution panel o All power cables are properly sized and terminated o A ground conductor is properly installed o Controller Area Network...

Page 121: ..._______________________________ _________________________________________________________________________ _________________________________________________________________________ ____________________...

Page 122: ...104 Eaton Power Xpert 9395P 600 300V 600V Installation and Operation Manual 164000710 Rev 07 Installation...

Page 123: ...ted for 5A maximum Power wiring should be a minimum of 22 AWG and a maximum of 14 AWG The wire should be rated for 1A minimum Use only 75 C copper wire 120 Vac for the RMP II RIM II or SCM II should b...

Page 124: ...d 1 Verify the UPS system is turned off and all power sources are removed See Chapter 7 UPS Operating Instructions for shutdown instructions 2 Unfasten the front door latch and swing the door open see...

Page 125: ...c CAN Bridge Card Interface Connections J3 Terminal Name Description 1 Alarm Programmable UPS alarm Activated by a remote dry contact closure 2 Alarm Return 3 Alarm Relay NC Normally closed contact op...

Page 126: ...r later use 4 Remove the interface entry conduit landing plates to drill or punch holes see Figure 30 5 Reinstall the interface entry plates and install the conduit 6 To locate the appropriate termina...

Page 127: ...ibuted bypass wiring purposes and is not a floor layout plan UPSs can be placed in any physical order Figure 50 Distributed Bypass System UPS CAN Wiring without MOBs Shielded Twisted Pair Shielded Twi...

Page 128: ...ield J3 10 Shield J3 10 Shield Figure 51 Distributed Bypass Pull Chain Wiring without MOBs 1 2 3 4 5 7 8 6 9 10 UPS 1 Twisted Pair Twisted Pair Twisted Pair Twisted Pair Twisted Pair Twisted Pair 1 2...

Page 129: ...37 Pull Chain Wiring Terminations From UPS 1 To UPS 2 To UPS 3 If Installed To UPS 4 If Installed TB2 1 Pull Chain TB2 1 Pull Chain TB2 1 Pull Chain TB2 1 Pull Chain TB2 2 Pull Chain Common TB2 2 Pul...

Page 130: ...E Always confirm contact operation prior to wiring 1 2 3 4 5 6 7 8 9 10 2 S P U 1 S P U 2 B T 2 B T 2 B T TB2 1 B T 1 B T 1 B T UPS 3 If Installed UPS 4 If Installed 1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7...

Page 131: ...mon Pull Chain Common UPS 4 CAN Bridge Card J3 1 Alarm MOB 4 Aux 1 NC MOB Open Alarm UPS 4 CAN Bridge Card J3 2 Alarm Return MOB 4 Aux 1 Com UPS 4 TB2 1 Pull Chain MOB 4 Aux 2 NO Pull Chain MOB 1 Aux...

Page 132: ...Figure 53 Figure 54 and Table 39 for the RMP II terminal location and wiring information NOTE 120 Vac for the RMP II should be supplied from the critical bus by facility planners or the customer 8 Ins...

Page 133: ...e a date 11 To check the operation of the RMP II ensure that the UPS is supplying the load via inverter or bypass If the indicators on the RMP II show the appropriate status then it is operating corre...

Page 134: ...all conduit between the UPS and RIM II See Figure 59 for RIM II knockout hole location 7 Install wiring between the UPS and RIM II See Figure 48 and Table 35 for the Hot Sync CAN Bridge Card terminal...

Page 135: ...na all S Su up pe er rv viis so or ry y C Co on nt ta ac ct t M Mo od du ulle e I II I To install SCM II wiring 1 Verify the UPS system is turned off and all power sources are removed See Chapter 7 UP...

Page 136: ...r the terminal location and wiring information Figure 56 Supervisory Contact Module II Terminal Location Ground Terminal Terminal TB1 Signal Connections from the UPS Terminal TB3 120 Vac Power Termina...

Page 137: ...Normal No Redundancy On Generator Bypass Not Available On Battery UPS Alarm On Bypass Shutdown Imminent NOTE Supervisory contacts are rated at 2 0A at 28 Vdc or 120 Vac and 0 15A at 115 Vdc NOTE Super...

Page 138: ...igure 58 through Figure 60 show the dimensions of the RMP II the RIM II and the SCM II Figure 58 Remote Monitor Panel II Dimensions Flush Mount using 10 Pan Head Screws Mount with vent holes facing up...

Page 139: ...59 Relay Interface Module II Dimensions Knockouts Provided on Five Surfaces Surface Mount using 10 Pan Head Screws for Hanging Mount with vent holes facing up Flush Mount using 10 Pan Head Screws Moun...

Page 140: ...Supervisory Contact Module II Dimensions Knockouts Provided on Five Surfaces Surface Mount using 10 Pan Head Screws for Hanging Mount with vent holes facing up Flush Mount using 10 Pan Head Screws Mo...

Page 141: ...is interrupted or falls outside the parameters specified in Chapter 10 Product Specifications the UPS uses a backup battery supply to maintain power to the critical load for a specified period of time...

Page 142: ...ly to the critical load through the continuous static switch and transfers automatically to Online mode if an abnormal condition is detected In Variable Module Management System VMMS mode the UPS oper...

Page 143: ...urns the UPS returns to Online mode NOTE Bypass mode is not available on a UPS configured as an IOM If the UPS becomes overloaded or unavailable the UPS switches to Bypass mode The UPS automatically r...

Page 144: ...s and also to allow the UPM to immediately return to active mode in the event of a disturbance or load step on the critical bus VMMS limits the maximum power available from a UPM when in VMMS mode The...

Page 145: ...pannes de courant lorsque l onduleur est en mode Contournement The static switch being an electronically controlled device can be turned on immediately to pick up the load from the inverter while the...

Page 146: ...support the customer s load without interruption If bypass is common with the rectifier input the backfeed protection contactor K5 also opens The opening of contactors K1 and K5 prevent system voltage...

Page 147: ...ery Converter Battery Battery Breaker Main Power Flow Trickle Current Energized De Energized Closed Open Breakers Contactors K2 Bypass Input Rectifier Input Output Input Breaker CB1 NOTE On a UPS conf...

Page 148: ...ne UPM Common Rectifier Feed Separate Battery Dual Feed Configuration Continuous Static Switch FI UPM Figure 68 Eaton 9395P 600 600 Eaton 9395P 600 550 Eaton 9395P 600 500 Eaton 9395P 600 450 Eaton 93...

Page 149: ...600 500 Eaton 9395P 600 450 Eaton 9395P 600 400 Single Reverse Transfer UPS Three UPM Common Rectifier Feed Common Battery IOM Configuration Figure 75 Eaton 9395P 600 600 Eaton 9395P 600 550 Eaton 939...

Page 150: ...Switch AC Input to UPS Rectifier 3 Wire A B C Rotation AC Input to Bypass 3 Wire A B C Rotation Interface Board Battery Aux Remote EPO Building Alarms Alarm Relays Fuse Battery Converter Inverter Out...

Page 151: ...Input to Bypass 3 Wire A B C Rotation Interface Board Battery Aux Remote EPO Building Alarms Alarm Relays Fuse Battery Converter Inverter Output Contactor K3 Fuse Rectifier Input Contactor K1 Battery...

Page 152: ...Board Battery Aux Remote EPO Building Alarms Alarm Relays Fuse Battery Converter Inverter Output Contactor K3 Fuse Rectifier Input Contactor K1 Battery Contactor K2 Fuse Fuse Fuse Battery Breaker BAT...

Page 153: ...Input to Bypass 3 Wire A B C Rotation Interface Board Battery Aux Remote EPO Building Alarms Alarm Relays Fuse Battery Converter Inverter Output Contactor K3 Fuse Rectifier Input Contactor K1 Battery...

Page 154: ...Contactor K3 Fuse Rectifier Input Contactor K1 Battery Contactor K2 Fuse Fuse Fuse UPM 1 Battery Breaker E4 E5 Battery Converter Inverter Output Contactor K3 Fuse Rectifier Input Contactor K1 Battery...

Page 155: ...Remote EPO Building Alarms Alarm Relays Fuse Battery Converter Inverter Output Contactor K3 Fuse Rectifier Input Contactor K1 Battery Contactor K2 Fuse Fuse Fuse UPM 1 Battery Breaker E4 E5 Battery C...

Page 156: ...ter Output Contactor K3 Fuse Rectifier Input Contactor K1 Battery Contactor K2 Fuse Fuse Fuse UPM 2 Battery Breaker E4 E5 Battery Converter Inverter Output Contactor K3 Fuse Rectifier Input Contactor...

Page 157: ...on Interface Board Battery Aux Remote EPO Building Alarms Alarm Relays Battery Converter Inverter Output Contactor K3 Fuse Rectifier Input Contactor K1 Battery Contactor K2 Fuse Fuse Fuse UPM 1 Batter...

Page 158: ...emote EPO Building Alarms Alarm Relays Battery Converter Inverter Output Contactor K3 Fuse Rectifier Input Contactor K1 Battery Contactor K2 Fuse Fuse Fuse UPM 1 Battery Breaker E4 E5 Battery Converte...

Page 159: ...s Battery Converter Inverter Output Contactor K3 Fuse Rectifier Input Contactor K1 Battery Contactor K2 Fuse Fuse Fuse UPM 2 Battery Breaker E4 E5 Not supplied with the UPS Battery Converter Inverter...

Page 160: ...ctor K3 Fuse Rectifier Input Contactor K1 Battery Contactor K2 Fuse Fuse Fuse UPM 1 Bypass Breaker CB4 Battery Converter Inverter Output Contactor K3 Fuse Rectifier Input Contactor K1 Battery Contacto...

Page 161: ...enance bypass a minimum of two separate feeds with upstream feeder breakers or a single feed with two upstream feeder breakers must be provided one for the UPS or rectifier input breaker RIB if instal...

Page 162: ...ty 2 0 if both UPMs in a system are required to support the load A parallel capacity system can also be redundant 2 1 as long as there is always one or more UPMs online than required to support the lo...

Page 163: ...inet or distribution panel for parallel systems up to four modules The applied load is shared equally among the available UPMs in the system Figure 77 shows the path of electrical power through the pa...

Page 164: ...pport the load If the load can be supported the system does not switch to bypass Figure 78 shows the path of electrical power through the parallel system when operating in Bypass mode In a distributed...

Page 165: ...o go to bypass 6 6 4 4 4 4 B Ba at tt te er ry y M Mo od de e D Diis st tr riib bu ut te ed d B By yp pa as ss s The UPSs transfer to Battery mode automatically if a utility power outage occurs or if...

Page 166: ...ring the battery discharge the input power becomes available again the rectifier begins to supply DC current to the inverter At this point the UPS returns to Online mode If at any time during the batt...

Page 167: ...tem Type Figure 80 Eaton 9395P 600 600 Eaton 9395P 600 550 Eaton 9395P 600 500 Eaton 9395P 600 450 Eaton 9395P 600 400 Eaton 9395P 600 300 Eaton 9395P 600 275 Eaton 9395P 600 250 Eaton 9395P 600 225 E...

Page 168: ...1 MOB 2 Not supplied with the UPS C E9 E10 E11 E12 D Battery Breaker Battery Converter Inverter K3 Fuse Rectifier K1 K2 Fuse Fuse Fuse E6 E7 E8 E12 K5 Static Switch Fuse E1 E2 E3 CB1 optional UPS 2 A...

Page 169: ...ectifier K1 K2 Fuse Fuse Fuse E6 E7 E8 E12 K5 Static Switch Fuse E1 E2 E3 CB1 optional UPS 2 A B E4 E5 BATTERY SYSTEM Not supplied with the UPS C E9 E10 E11 E12 D Battery Breaker Battery Converter Inv...

Page 170: ...ATTERY SYSTEM Not supplied with the UPS C E9 E10 E11 E12 D Battery Breaker Battery Converter Inverter K3 Fuse Rectifier K1 K2 Fuse Fuse Fuse E6 E7 E8 E12 K5 Static Switch Fuse E1 E2 E3 CB1 optional UP...

Page 171: ...E 2 Read this section of the manual and have thorough knowledge of UPS operation before attempting to operate any of the controls NOTE 3 The UPS displays two minutes of battery runtime at the initial...

Page 172: ...en n C Co on nt tr ro oll P Pa an ne ell This section describes how the various screens are used to control and monitor UPS operation Figure 83 shows the location of the color touchscreen control pan...

Page 173: ...ly The power module is supplying power to the critical load Yellow Lit Steady The UPS is in Battery mode Because Battery mode is a normal condition of the UPS the Normal indicator also remains illumin...

Page 174: ...is installed the temperature and humidity sensed by the probe will also be displayed The small head symbol between the system model and time allows the operator select a different language from an imb...

Page 175: ...in ng g t th he e M Ma aiin n M Me en nu u B Bu ut tt to on ns s The UPS menu bar shown in Figure 86 allows you to display data in the information area to help you monitor and control UPS operation Ta...

Page 176: ...nate language NOTE On all screens Black lines indicate NO power flow Green lines indicate ACTIVE power flow Yellow lines indicates an out of tolerance condition NOTE Screens shown are representative e...

Page 177: ...Online Mode See Output KVA figure See Average Efficiency figure See Consumption figure Touching the LOAD kVA button displays the Output kVA screen shown in Figure 89 Figure 89 Output kVA Screen from...

Page 178: ...splays the screen in Figure 91 Figure 91 Consumption Screen from Home Screen 7 7 3 3 5 5 P Po ow we er r M Ma ap ps s S Sc cr re ee en n B By yp pa as ss s M Mo od de e Figure 92 shows the Bypass scre...

Page 179: ...e of a command request confirmation pop up screen This type of pop up allows the user to confirm that the requested command is valid Figure 93 Typical Command Confirmation Screen Charger Off 7 7 3 3 7...

Page 180: ...tion over various time periods of 24 hours 7 days 30 days or 1 year This is true of all the meters screens listed in the top section Figure 94 Meters Summary Screen See Average Efficiency Figure See C...

Page 181: ...v 07 163 Figure 95 Input Meters Screen The Bypass Meters Screen shown in Figure 96 displays values pertaining to the Bypass conditions Figure 96 Bypass Meters Screen The Output Meters Screen shown in...

Page 182: ...Me et te er rs s D De et ta aiill S Sc cr re ee en n Figure 98 shows the Input Meters detail screen This screen displays the individual values of the system in additional detail The Bypass Output and...

Page 183: ...reen shown in Figure 99 allows the operator to choose the individual source for system readings Figure 99 Select Source Screen 7 7 3 3 1 10 0 B Ba at tt te er ry y M Me et te er rs s S Sc cr re ee en...

Page 184: ...166 Eaton Power Xpert 9395P 600 300V 600V Installation and Operation Manual 164000710 Rev 07 Figure 101 shows the Battery Log access screen Figure 101 Battery Log Screen UPS Operating Instructions...

Page 185: ...tallation and Operation Manual 164000710 Rev 07 167 Figure 102 shows the Battery Log Detail screen Figure 102 Battery Log Detail Figure 103 shows the Battery Log Summary screen Figure 103 Battery Log...

Page 186: ...f second rate System Event Indicators The status indicators on the UPS control panel work with the event horn to let the operator know when the UPS is operating in any mode other than normal Only the...

Page 187: ...106 User Log Detail Screen 7 7 3 3 1 13 3 S Sy ys st te em m S St ta at tu us s S Sc cr re ee en n a an nd d C Co on nt tr ro olls s Press the SYSTEM CONTROLS pushbutton on the main menu bar to displa...

Page 188: ...and displays the state of the UPM Figure 107 shows the System Status screen Figure 107 System Status Screen Figure 108 shows the Module Controls screen This screen allows control of the individual mod...

Page 189: ...108 the user can observe full details of an individual module It also allows the user to move through various modules and modes while within this screen Figure 109 Module Control Detail Screen The Me...

Page 190: ...3 3 1 14 4 S Se et tt tiin ng gs s S Sc cr re ee en n The screen shown in Figure 112 gives the operator access to basic system information such as serial number installed firmware version etc Touching...

Page 191: ...system values Figure 113 Configuration Options Screen 7 7 3 3 1 16 6 E En ne er rg gy y A Ad dv va an nt ta ag ge e A Ar rc ch hiit te ec ct tu ur re e E EA AA A S Sc cr re ee en n This screen shown i...

Page 192: ...4 Energy Advantage Architecture EAA Screen This screen shown in Figure 115 asks the operator to verify disabling the ESS mode running at that time Figure 115 Disable ESS Screen This screen shown in Fi...

Page 193: ...16 High Alert Timer Screen 7 7 3 3 1 17 7 S St ta at tiis st tiic cs s B Ba as siic c S Sc cr re ee en n The screen shown in Figure 117 allows the operator to query the system for various operational...

Page 194: ...S C Co om mp pa ar riis so on n S Sc cr re ee en n The screen shown Figure 119 allows the operator to visually obtain EAA mode efficiency values Figure 119 ESS Comparison Screen 7 7 3 3 1 19 9 U UP P...

Page 195: ...al 164000710 Rev 07 177 Figure 120 UPS Module Map Screen 7 7 3 3 2 20 0 S Sy ys st te em m O Ov ve er rv viie ew w S Sc cr re ee en n The screen shown Figure 121 displays values for all UPS and UPM pa...

Page 196: ...e input breaker CB1 6 Close the door and secure the latch 7 Observe the UPS control panel display becoming active indicating logic power 8 Press the LOCK icon on the main screen The Sign In screen is...

Page 197: ...ance est d clench l tape suivante N utiliser cette fonction que pour mettre la charge critique hors tension NOTE The following instructions are for the Eaton supplied REPO switch If a customer supplie...

Page 198: ...en prompts to get to the proper screen The operator cannot inadvertently cause a system dump or disconnect unless they override a warning pop up Value or information screens DO NOT affect system opera...

Page 199: ...It takes approximately one minute for the UPS to achieve Online mode The Online status indicator is illuminated The UPS status indicates ONLINE on the header section of the screen The UPM status indic...

Page 200: ...t breaker CB1 6 Close the door and secure the latch 7 Observe the UPS control panel becoming active indicating logic power 8 Press the CONTROLS pushbutton on the main menu bar The System Status screen...

Page 201: ...s SHUTDOWN The power module is turned off The remaining UPMs continue to supply the critical load Logic power remains on 7 7 5 5 5 5 S Siin ng glle e U UP PM M R Re es st ta ar rt t To restart a singl...

Page 202: ...critical load 7 Perform the LOAD OFF procedure in paragraph 7 5 11 Using the UPS LOAD OFF Pushbutton or paragraph 7 5 12 Using the UPS LOAD OFF Command on the UPS being shut down The input output bat...

Page 203: ...nd the power module is turned off Logic power remains on 11 If there are other UPMs in the UPS they should be shut down in sequence Repeat Steps 7 through 10 until all other UPMs are shut down 12 Perf...

Page 204: ...other online paralleled UPSs the UPS will not go to bypass during startup The UPS will start sync to the other UPSs online and go online 16 Verify the following messages display sequentially on the U...

Page 205: ...menu bar 7 7 5 5 1 11 1 U Us siin ng g t th he e U UP PS S L LO OA AD D O OF FF F P Pu us sh hb bu ut tt to on n A UPS Load Off is initiated by either a command or a pushbutton It controls the UPSs o...

Page 206: ...system unless all UPSs have been transferred to bypass To immediately shut down the whole system use the REPO switch see paragraph 7 5 13 Using the Remote Emergency Power off Switch All power to the c...

Page 207: ...ture only when you want to de energize the critical load NOTE The following instructions are for the Eaton supplied REPO switch If a customer supplied REPO switch is used it may not activate in the sa...

Page 208: ...190 Eaton Power Xpert 9395P 600 300V 600V Installation and Operation Manual 164000710 Rev 07 UPS Operating Instructions...

Page 209: ...lding Management System BMS using the Modbus RTU protocol Relay Interface Card AS 400 has isolated dry contact Form C relay outputs for UPS status Utility failure Low battery UPS alarm OK or On bypass...

Page 210: ...This allows you to collaborate and Eaton to notify the most appropriate person responsible for a specific site or device Real time access to key performance information alarms and trended health data...

Page 211: ...n an unlimited number also available Contact your Eaton Sales representative for additional information 8 8 4 4 B Bu uiilld diin ng g A Alla ar rm m M Mo on niit to or riin ng g This standard feature...

Page 212: ...r Xpert 9395P 600 300V 600V Installation and Operation Manual 164000710 Rev 07 Figure 124 Remote Monitor Panel II The RMP II contains a local horn and the backlit status indicators listed in Table 45...

Page 213: ...is means that the UPS is not energized The load is not protected in Bypass mode and a horn sounds after 30 seconds UPS ALARM The UPS system is issuing an alarm Conditions that affect the current UPS m...

Page 214: ...pin connectors labeled J1 through J4 Figure 125 Relay Interface Module II The RIM II can provide the status and alarm signals shown in Table 46 Table 46 Customer Interface Connectors Status J1 throug...

Page 215: ...an be flush mounted or surface mounted on a desktop or secured to a wall Figure 126 shows the SCM II Figure 126 Supervisory Contact Module II The SCM II provides signals for the indications shown in T...

Page 216: ...198 Eaton Power Xpert 9395P 600 300V 600V Installation and Operation Manual 164000710 Rev 07 Communication...

Page 217: ...t make any assumptions about the electrical state of any cabinet in the UPS system AVERTISSEMENT L installation et l entretien ne doivent tre effectu s que par du personnel qualifi PR SENCE DE TENSION...

Page 218: ...ronment is within the parameters specified in paragraph 3 2 3 Installation Considerations and Chapter 10 Product Specifications 4 Ensure the UPS is in Online mode Online status indicator is illuminate...

Page 219: ...n unfasten the front door latch and swing the door open See Figure 20 4 Pull the foam filters over the screw heads on the cabinet mounted studs and remove the filters from the cabinet 5 Push the washe...

Page 220: ...presentative for a replacement filter To remove the filter a Remove one top screw and two bottom screws securing the FI UPM front panel refer to the Eaton Power Xpert 9395P UPS Field Installed UPM Mec...

Page 221: ...ce e Contact an Eaton service representative for battery maintenance Battery replacement and maintenance should be performed only by authorized service personnel 9 9 3 3 I In ns st ta alllliin ng g B...

Page 222: ...ets dangereux NO DISPOSAL Do not discard waste electrical or electronic equipment WEEE in the trash For proper disposal contact your local recycling reuse or hazardous waste center ATTENTION Ne pas li...

Page 223: ...50 kVA 50 60 Hz Eaton 9395P 600 225 one or two UPM 600 kVA 225 kVA 50 60 Hz Eaton 9395P 600 200 one or two UPM 600 kVA 200 kVA 50 60 Hz 1 10 0 2 2 S Sp pe ec ciif fiic ca at tiio on ns s The following...

Page 224: ...UPM models See Table 9 or Table 10 for 575V One Two Three UPM models See Table 11 or Table 12 for 480V One Two Three UPM models See Table 13 or Table 14 for 415V One Two Three UPM models See Table 15...

Page 225: ...F Operating Altitude Maximum 1000 m 3000 ft at 40 C without derating Storage Temperature 25 to 60 C excluding batteries prolonged storage above 40 C causes rapid battery self discharge Relative Humidi...

Page 226: ...16400071007 164000710 07...

Reviews: