138
Eaton
®
Power Xpert
®
9395P-600 (300V-600V) Installation and Operation Manual 164000710—Rev 07
Figure 71. Two UPM, Common Rectifier Feed, Separate Battery, Dual-Feed Configuration, Continuous
Static Switch, FI-UPM
Input Breaker
(CB1)
(optional)
E1, E2, E3
E6, E7,
E8, E12
UPS CABINET
Backfeed
Contactor (K5)
Static
Switch
AC Input to
UPS Rectifier
3 Wire A-B-C
Rotation
AC Input to
Bypass
3 Wire A-B-C
Rotation
Fuse
Battery
Converter
Inverter
Output
Contactor
(K3)
Fuse
Rectifier
Input
Contactor
(K1)
Battery Contactor (K2)
Fuse
Fuse
Fuse
UPM 1
Battery
Breaker
E4, E5
Battery
Converter
Inverter
Output
Contactor
(K3)
Fuse
Rectifier
Input
Contactor
(K1)
Battery Contactor (K2)
Fuse
Fuse
Fuse
UPM 2
Battery
Breaker
E4, E5
Battery
Converter
Inverter
Output
Contactor
(K3)
Fuse
Rectifier
Input
Contactor
(K1)
Battery Contactor (K2)
Fuse
Fuse
Fuse
X-Slot
Interface
48V Battery
Shunt Trip
Interface Board
Battery Aux
Remote EPO
Building Alarms
Alarm Relays
FI-UPM CABINET
A
B
C
D
C
AC Output
to Critical
Load
C
BATTERY SYSTEM
(Not supplied with the UPS)
BATTERY SYSTEM
(Not supplied with the UPS)
Single-Feed Kit
(Not supplied
with the UPS)
E4, E5
E9,
E10,
E11,,
E12
Battery
Breaker
BATTERY SYSTEM
(Not supplied with the UPS)
FI-UPM
NOTE
Callout letters
A
,
B
,
C
, and
D
map to the applicable Input/Output Ratings and External Wiring Requirements Table in Chapter 3.