4
Eaton
®
Power Xpert
®
9395P-600 (300V-600V) Installation and Operation Manual 164000710—Rev 07
11..22
S
Siinnggllee U
UP
PM
M P
Plluuss 11 aanndd TTw
woo U
UP
PM
M P
Plluuss 11 C
Coonnffiigguurraattiioonnss
The optional Single UPM Plus 1 9395P-600 UPS configuration has three sections:
•
an ISBM section configured either as an integrated system bypass module (ISBM) or an input output
module (IOM) rated for a maximum of 600 kVA
•
a UPM section with one UPM
•
one field-installed UPM (FI-UPM), which is field upgraded and provides N+1 redundancy for the basic
configuration
The optional Two UPM UPS 9395P-600 configuration has three sections:
•
an ISBM section configured either as an integrated system bypass module (ISBM) or an input output
module (IOM) rated for a maximum of 900 kVA
•
a UPM section with two UPMs l one field-installed UPM (FI-UPM), which is field upgraded and provides N
+1 redundancy for the basic configuration
For Plus 1 field upgrades to all models, the FI-UPM is shipped separately and is added later to the left of the
existing configuration (see
and
Figure 3. Standard Single UPM and Two UPM, Plus 1 FI-UPM UPS Configurations (all except the 600V
model)
FI-UPM
ISBM
UPM
UPM
ISBM
UPM
FI-UPM
Standard ISBM and 2 x UPM Section, Upgraded with
Plus 1 Field Installed FI-UPM
(380V, 400V, 415V, and 480V)
Standard ISBM and 1 x UPM Section, Upgraded with
Plus 1 Field Installed FI-UPM
(380V, 400V, 415V, and 480V)
Summary of Contents for Power Xpert 9395P-600/600
Page 8: ......
Page 226: ...16400071007 164000710 07...