Figure 128. FI-UPM Section Air Filter Locations
FI-UPM Air Filter
9.
If the UPS configuration included an FI-UPM model, check the FI-UPM air filter (located behind the front
panel) and wash or replace as necessary. See for the filter location. The FI-UPM filter size is 20" x 44" x
0.25". Contact an Eaton service representative for a replacement filter. To remove the filter:
a.
Remove one top screw and two bottom screws securing the FI-UPM front panel (refer to the
Eaton
®
Power Xpert
®
9395P UPS Field Installed UPM Mechanical Installation Manual (P-164000503)).
. Lift
the panel straight up to remove it from the panel hanger bracket at the top of the cabinet.
b.
Pull the foam filter over the screw heads on the cabinet mounted studs and remove the filter from the
cabinet.
Verify washed filter is thoroughly dry before reinstalling.
ATTENTION!
Vérifier que les filtres sont bien secs avant de les réinstaller.