NOTE
Eaton battery cabinets are located in the same room as the UPS, the battery cabinet
environmental requirements supersede the UPS requirements. Operating temperatures
above the recommended range will result in decreased battery life and performance,
and will reduce or void the battery warranty. Refer to Eaton's Terms and Conditions of
Sale with Battery Replacement Coverage and the Battery Replacement Price Book for
more information. These documents can be found at www.eaton.com/powerquality or
contact an Eaton service representative for information on how to obtain copies.
The UPS ventilation requirements are shown in
through
.
Table 4. 600V Air Conditioning and Ventilation Requirements During Full Load Operation
Model
Rating
Input/Output
Voltage
Heat Rejection
BTU/hr x1000
(kg-cal/hr)
Ventilation Required for
Cooling Air Exhaust
Eaton 9395P-600/550
(CSS or IOM)
550 kVA
550 kVA
600/600
30.4 (103.8)
Approximately 2383 liter/sec (5050 CFM)
Eaton 9395P-600/500
(CSS or IOM)
500 kVA
500 kVA
600/600
27.6 (94.3)
Eaton 9395P-600/450
(CSS or IOM)
450 kVA
450 kVA
600/600
24.9 (84.9)
Eaton 9395P-600/400
(CSS or IOM)
400 kVA
400 kVA
600/600
22.1 (75.5)
Eaton 9395P-600/300
(CSS or IOM)
300 kVA
300 kVA
600/600
16.6 (56.6)
Approximately 1321 liter/sec (2800 CFM)
With Field Installed UPM:
Approximately 2265 liter/sec (4800 CFM)
NOTE CSS = Continuous Static Switch; IOM = Input Output Module
The UPS 480V ventilation requirements are shown in
.
Table 5. 480V Air Conditioning and Ventilation Requirements During Full Load Operation
Model
Rating
Input/Output
Voltage
Heat Rejection
BTU/hr x1000
(kg-cal/hr)
Ventilation Required for
Cooling Air Exhaust
Eaton 9395P-600/600
(CSS or IOM)
600 kVA
600 kVA
480/480
23.1 (78.7)
Approximately 2383 liter/sec (5050 CFM)
Eaton 9395P-600/550
(CSS or IOM)
550 kVA
550 kVA
480/480
21.1 (72.2)
Eaton 9395P-600/500
(CSS or IOM)
500 kVA
500 kVA
480/480
18.7 (63.8)
Eaton 9395P-600/450
(CSS or IOM)
450 kVA
450 kVA
480/480
15.8 (54.1)
Eaton 9395P-600/400
(CSS or IOM)
400 kVA
400 kVA
480/480
14.1 (48.1)
Eaton 9395P-600/300
(CSS or IOM)
300 kVA
300 kVA
480/480
11.5 (39.4)
Approximately 1321 liter/sec (2800 CFM)
With Field Installed FI-UPM:
Approximately 2265 liter/sec (4800 CFM)
Eaton 9395P-600/275
(CSS or IOM)
275 kVA
275 kVA
480/480
10.6 (36.1)