9395P-600 (300V-600V) Installation and Operation Manual 164000710—Rev 07
59
Recommended disconnect size is based on a maximum full load discharge time less than 3 hours. For longer
discharge times a larger disconnect may be required.
Table 31. Recommended DC Input Battery Disconnect Ratings 100% – Common Battery
UPS Model
All Ratings
Eaton 9395P-600/600
Eaton 9395P-600/550
Eaton 9395P-600/500
1600A
Eaton 9395P-600/450
Eaton 9395P-600/400
1200A
Eaton 9395P-600/300
Eaton 9395P-600/275
Eaton 9395P-600/250
Eaton 9395P-600/225
Eaton 9395P-600/200
See Note
1600A
NOTE Bypass conduit data is not applicable to IOM configurations.
Table 32. Recommended DC Input Battery Disconnect Ratings 100% – Separate Battery
UPS Model
All Ratings
Eaton 9395P-600/600
Eaton 9395P-600/300
800A
Eaton 9395P-600/550
Eaton 9395P-600/500
Eaton 9395P-600/400
Eaton 9395P-600/250
Eaton 9395P-600/225
Eaton 9395P-600/200
See Note
700A
NOTE Bypass conduit data is not applicable to IOM configurations.
33..22..77
U
UP
PS
S S
Syysstteem
m IInntteerrffaaccee W
Wiirriinngg P
Prreeppaarraattiioonn
Control wiring for features and options should be connected at the customer interface terminal blocks located
inside the UPS.
Do not directly connect relay contacts to the mains related circuits. Reinforced insulation to the mains is
required.
ATTENTION!
Ne pas directement brancher les contacts de relais aux circuits du réseau. Une isolation renforcée des réseaux
est nécessaire.