78
Eaton
®
Power Xpert
®
9395P-600 (300V-600V) Installation and Operation Manual 164000710—Rev 07
NOTE
Remove the ISBM section top or bottom conduit landing plate to drill or punch conduit
holes (see
Use the procedures in the following paragraphs to connect the external and battery power wiring.
44..88..11
22--H
Hoollee B
Baarrrreell LLuugg TTeerrm
miinnaattiioonnss ffoorr B
Buuss B
Baarr IInnssttaallllaattiioonn
Paragraphs
External Power Wiring Installation
and
require connecting input,
output, and battery power wiring using 2-hole barrel lugs. See
for the hardware sequence when
installing the lugs to the bus bars. Tighten the nut to the torque value listed in
.
NOTE
Conical washers are special purpose washers that look similar to flat washers, except
for a slight conical shape. When installing conical washers, the top of the dome should
be next to the nut and the base of the washer should be against a flat washer, or large
terminal.
One set of bolts secure the bus bar. (See Single and Double Lug Installation in
). Other bolts are used
for the input and output cable connections. (See Cable Connection Bolt Orientation in
). Always insert
the cable connection bolt with the bolt head side closest to the transformer. This avoids interference with the
bolt that holds the bus bar.
Figure 28. Typical Bus Bar Barrel Lug Mounting – Hardware Assembly Sequence
Double Lug Installation
Cable Connection Bolt Orientation
Hex Nut
Conic al Washer
Lug
Bus Bar
Flat Washer
Bolt Head
Lug
Flat Washer
Single Lug Installation
Hex Nut
Conic al Washer
Lug
Bus Bar
Flat Washer
Bolt Head
Flat Washer
Transformer Side
Connector
Sleeves
Conical Washer
Nut and Flat Washer
Bolt Head
and Flat Washer
Summary of Contents for Power Xpert 9395P-600/600
Page 8: ......
Page 226: ...16400071007 164000710 07...