79
44..88..22
EExxtteerrnnaall P
Poow
weerr W
Wiirriinngg IInnssttaallllaattiioonn
To install wiring to connections:
1.
Remove one top screw and two bottom screws securing each ISBM section left and right front panel (see
). Lift the panels straight up to remove them from the panel hanger brackets at the top of the
cabinet.
2.
Remove the screws securing the top and bottom internal safety shield panels and remove the panels to
gain access to the input, output, and battery terminals. Retain the hardware for later use.
3.
Route the input and output cables through either the top or bottom of the cabinet to the UPS terminals.
See
through
for wiring access information and terminal locations.
Top Access Wiring
. Remove the top conduit plate from the top of the ISBM section. Identify all conduit
requirements and mark their location. Drill and punch all conduit holes in the top conduit plate prior to
mounting on the ISBM section. Install the conduit plate and install all conduit runs into the plate. Pull wiring
through conduit into the ISBM section wiring area.
Bottom Access Wiring
. Remove the bottom conduit plate from the inside bottom of the ISBM section.
Identify all conduit requirements and mark their location. Drill and punch all conduit holes in the bottom
conduit plate prior to mounting on the ISBM section. Install the conduit plate and install all conduit runs
into the plate. Pull wiring through conduit into the ISBM section wiring area.
Figure 29. ISBM and UPM Section Debris Shields
Ventilation Grill Debris Shields
Remove shields before operating system