Installing Options and Accessories
Eaton
®
Power Xpert
®
9395P-900 UPS Installation and Operation Manual P-164000501—Rev 09
www.eaton.com/powerquality
5-5
Figure 5-3. Distributed Bypass System CAN and Pull-Chain Simplified Interface Wiring
Figure 5-4. Distributed Bypass System UPS CAN Wiring without MOBs
UPS 1
UPS 2
UPS 3
UPS 4
CAN
(If Installed)
(If Installed)
Pull Chain
NOTE
This drawing is for distributed bypass wiring purposes and is not a floor layout plan. UPSs can be placed in any physical order
.
Shielded Twisted Pair
Shielded Twisted Pair
Shielded Twisted Pair
UPS 1
CAN Bridge Card J3
UPS 2
CAN Bridge Card J3
UPS 3
CAN Bridge Card J3
(If Installed)
UPS 4
CAN Bridge Card J3
(If Installed)
NOTE
External CAN connections between UPSs require shielded twisted pair wire.
Table 5-2. CAN Bridge Card Wiring Terminations
From
UPS 1 CAN Bridge Card
To
UPS 2 CAN Bridge Card
To
UPS 3 CAN Bridge Card
(If Installed)
To
UPS 4 CAN Bridge Card
(If Installed)
J3–8 (L)
J3–8 (L)
J3–8 (L)
J3–8 (L)
J3–9 (H)
J3–9 (H)
J3–9 (H)
J3–9 (H)
J3–10 (Shield)
J3–10 (Shield)
J3–10 (Shield)
J3–10 (Shield)