Eaton
®
Power Xpert
®
9395P-900 UPS Installation and Operation Manual P-164000501—Rev 09
www.eaton.com/powerquality
6-1
Chapter 6
Understanding UPS Operation
6.1
UPS System Overview
The Eaton Power Xpert 9395P-900 UPS is a continuous-duty, solid-state, transformerless (at 480 Vac),
three-phase, true online system that provides conditioned and uninterruptible AC power to the UPS system's
output and critical load.
The basic system consists of a rectifier, battery converter, inverter, monitoring/operation control panel,
integrated communication server, and digital signal processor (DSP) logic. Figure 6-1 shows the main elements
of the UPS system.
If utility power is interrupted or falls outside the parameters specified in Chapter 10, “Product Specifications”
the UPS uses a
backup battery supply
to maintain power to the critical load for a specified period of time or
until the utility power returns. For extended power outages, the UPS system allows you to either transfer to an
alternative power system (such as a generator) or shut down your critical load in an orderly manner.
Figure 6-1. Main Elements of the UPS System
The emergency bypass consists of a continuous static switch, and a backfeed protection contactor K5. The
bypass breaker (if installed) is located in parallel with the static switch. The backfeed protection contactor is
located in series with the static switch. The static switch is armed and ready during normal operation.
Output
Contactor
K3
Battery
Battery
Breaker
Battery
Converter
Input
Contactor
K1
AC Input to
Rectifier/
Charger
AC Input to
Bypass
Backfeed
Protection
Contactor
K5
Power Module
Inverter
Rectifier
Digital
Metering
Static
Switch
AC Output
to Critical
Load
UPS Cabinet
Battery
Contactor
K2
Battery System
Input
Breaker
CB1
(optional)
NOTE
On a UPS configured as an Input Output Module (IOM), the bypass input, static switch, and backfeed protection
contactor (K5) are not present.