The UPS ventilation requirements are shown in Table 3-3.
Table 3-3. 480V Air Conditioning and Ventilation Requirements During Full Load Operation
Model
Rating
Input/Output
Voltage
Heat Rejection
kW (1000 BTU/hr)
Ventilation Required for Cooling Air Exhaust
Eaton 9395P-900/900*
(CSS)
900 kVA
900 kVA
480/480
34.6 (118)
Approximately 3300 liter/sec (7000 CFM)
With field installed UPM:
Approximately 4250 liter/sec (9000 CFM)
Eaton 9395P-900/900
(CSS or IOM)
900 kVA
825 kW
480/480
31.7 (108.3)
Eaton 9395P-900/825
(CSS)
825kVA
825 kW
480/480
31.7 (108.3)
Eaton 9395P-900/750
(CSS)
750 kVA
750 kW
480/480
28.0 (95.6)
Eaton 9395P-900/675
(CSS)
675 kVA
675 kW
480/480
23.8 (81.1)
Eaton 9395P-900/600*
(CSS)
600 kVA
600 kVA
480/480
23.1 (78.7)
Approximately 2400 liter/sec (5000 CFM)
Eaton 9395P-900/600
(CSS)
600 kVA
550 kW
480/480
21.1 (72.2)
Eaton 9395P-900/550
(CSS)
550 kVA
550 kW
480/480
21.1 (72.2)
Eaton 9395P-900/500
(CSS)
500 kVA
500 kW
480/480
18.7 (63.8)
Eaton 9395P-900/450
(CSS)
450 kVA
450 kW
480/480
15.8 (54.1)
NOTE CSS = Continuous Static Switch; IOM = Input Output Module
Table 3-4. 415V Air Conditioning and Ventilation Requirements During Full Load Operation
Model
Rating
Input/Output
Voltage
Heat Rejection
kW (1000 BTU/hr)
Ventilation Required for Cooling Air Exhaust
Eaton 9395P-900/825
(CSS)
825kVA
825 kW
415/415
34.0 (116.1)
Approximately 3300 liter/sec (7000 CFM)
With field installed UPM:
Approximately 4250 liter/sec (9000 CFM)
Eaton 9395P-900/750
(CSS)
750 kVA
750 kW
415/415
30.9 (105.6)
Eaton 9395P-900/675
(CSS)
675 kVA
675 kW
415/415
27.8 (95.0)
Eaton 9395P-900/600
(CSS)
600 kVA
550 kW
415/415
24.7 (84.5)
Approximately 2400 liter/sec (5000 CFM)
Eaton 9395P-900/550
(CSS)
550 kVA
550 kW
415/415
22.7 (77.4)
Eaton 9395P-900/500
(CSS)
500 kVA
500 kW
415/415
20.6 (70.4)
Eaton 9395P-900/450
(CSS)
450 kVA
450 kW
415/415
18.5 (63.3)
NOTE CSS = Continuous Static Switch; IOM = Input Output Module
Summary of Contents for Power Xpert 9395P-900 Series
Page 2: ......
Page 8: ...This page intentionally left blank...
Page 33: ...Section I Installation...
Page 34: ......
Page 139: ...Section II Operation...
Page 140: ......
Page 231: ......
Page 232: ...P 164000501 6 P 164000501 9...