Eaton
®
Power Xpert
®
9395P-900 UPS Installation and Operation Manual P-164000501—Rev 09
www.eaton.com/powerquality
10-1
Chapter 10 Product Specifications
10.1
Model Numbers
The UPS is housed in two or three free-standing cabinets, divided into two or three sections with safety shields
behind the door and front panels. The UPS is available in 50 or 60 Hz with various output power ratings.
10.2
Specifications
The following sections detail the input, output, environmental, and battery specifications for the UPS.
10.2.1 UPS Input
The following sections detail the input, output, environmental, and battery specifications for the UPS.
Models
Power Rating
Frequency
Eaton 9395P-900/900* (three or four UPM)
900 kVA, 900 kW
50/60 Hz
Eaton 9395P-900/900 (three or four UPM)
900 kVA, 825 kW
50/60 Hz
Eaton 9395P-900/825 (three or four UPM)
825 kVA, 825 kW
50/60 Hz
Eaton 9395P-900/750 (three or four UPM)
750 kVA, 750 kW
50/60 Hz
Eaton 9395P-900/675 (three or four UPM)
675 kVA 675 kW
50/60 Hz
Eaton 9395P-900/600* (three or four UPM)
600 kVA 600 kW
50/60 Hz
Eaton 9395P-900/600 (two or three UPM)
600 kVA 550 kW
50/60 Hz
Eaton 9395P-900/550 (two or three UPM)
550 kVA 550 kW
50/60 Hz
Eaton 9395P-900/500 (two or three UPM)
500 kVA 500 kW
50/60 Hz
Eaton 9395P-900/450 (two or three UPM)
450 kVA 450 kW
50/60 Hz
Operating Input Voltage
480 Vac
Operating Input Frequency Range
50/60 Hz
Operating Input Current
See Table 3-7 or Table 3-8 for 480V three UPM models.
See Table 3-9 or Table 3-10 for 480V two UPM models.
See Table 3-11 or Table 3-12 for 415V three UPM models.
See Table 3-13 or Table 3-14 for 400V three UPM models.
See Table 3-15 or Table 3-16 for 380V three UPM models.
Reduced for Generator
Adjustable
Input Current Harmonic Content
3% THD at full load
Power Factor
Minimum 0.99 at full load
Line Surges
6 kV OC, 3 kA SC per ANSI 62.41 and IEC 801-4
Battery Voltage
480 Vdc
Battery Charging Capacity
Configurable per UPM at nominal line voltage:
Up to 120A
Battery Shunt Trip
48 Vdc