UPS Installation Plan and Unpacking
Eaton
®
Power Xpert
®
9395P-900 UPS Installation and Operation Manual P-164000501—Rev 09
www.eaton.com/powerquality
3-29
Terminals E1 through E11 are 2-hole busbar mountings for standard NEMA 2-hole barrel lugs. The power wiring
connections for this equipment are rated at 90°C. See Table 3-19 for power cable terminations, Table 3-20 for
supplied terminal hardware, and Table 3-21 for recommended installation parts and tools not supplied by Eaton.
Figure 4-17 through Figure 4-20 show the location of the power cable terminals inside the UPS.
Table 3-19. UPS External Power Cable Terminations for Three/Four UPM Models
Terminal Function
Terminal
Function
Bus Landings
(using both sides of bus)
Tightening Torque
Nm (lb ft)
Bolt Size
AC Input to UPS Rectifier
E1
Phase A
6 – 2 bolt mounting
76 (56)
M12
E2
Phase B
6 – 2 bolt mounting
76 (56)
M12
E3
Phase C
6 – 2 bolt mounting
76 (56)
M12
AC Input to Bypass
E6
Phase A
6 – 2 bolt mounting
76 (56)
M12
E7
Phase B
6 – 2 bolt mounting
76 (56)
M12
E8
Phase C
6 – 2 bolt mounting
76 (56)
M12
AC Output to Critical Load
E9
Phase A
6 – 2 bolt mounting
76 (56)
M12
E10
Phase B
6 – 2 bolt mounting
76 (56)
M12
E11
Phase C
6 – 2 bolt mounting
76 (56)
M12
DC Input from Battery or
Battery Disconnect to UPS –
Common Battery
E4
Battery (+)
16 – 2 bolt mounting
76 (56)
M12
E5
Battery (-)
16 – 2 bolt mounting
76 (56)
M12
DC Input from Battery or
Battery Disconnect to UPS –
Separate Battery (UPM 1)
E4
Battery (+)
4 – 2 bolt mounting
76 (56)
M12
E5
Battery (-)
4 – 2 bolt mounting
76 (56)
M12
DC Input from Battery or
Battery Disconnect to UPS –
Separate Battery (UPM 2)
E4
Battery (+)
4 – 2 bolt mounting
76 (56)
M12
E5
Battery (-)
4 – 2 bolt mounting
76 (56)
M12
DC Input from Battery or
Battery Disconnect to UPS –
Separate Battery (UPM 3)
E4
Battery (+)
4 – 2 bolt mounting
76 (56)
M12
E5
Battery (-)
4 – 2 bolt mounting
76 (56)
M12
DC Input from Battery or
Battery Disconnect to UPS –
Separate Battery (UPM 4
FI-UPM)
E4
Battery (+)
4 – 2 bolt mounting
76 (56)
M12
E5
Battery (-)
4 – 2 bolt mounting
76 (56)
M12
Input and Output Neutral
E12
Neutral
12 – 2 bolt mounting
76 (56)
M12
Customer Ground
Ground
Ground
15 – 2 bolt mounting
76 (56)
M12
NOTE
V
NOTE
V
Bypass terminations are not applicable to IOM configurations.