UPS Installation Plan and Unpacking
3-34
Eaton
®
Power Xpert
®
9395P-900 UPS Installation and Operation Manual P-164000501—Rev 09
www.eaton.com/powerquality
External overcurrent protection and disconnect are not provided by this product, but are required by codes.
Refer to Refer to Table 3-7 to Table 3-10 for wiring requirements. If an output lockable disconnect is required,
it is to be supplied by the customer.
100% breaker ratings for rectifier input.
Eaton 9395P-900/450
See Note 1
400 Vac
380 Vac
AC Input to UPS Rectifier
(A, B, C, Ground)
4
3
4
AC Input to Bypass and Output
(A, B, C, Ground)
4
3
4
DC
(Common Battery)
Battery
(Positive, Negative, Ground)
6
3
6
All models
DC (Separate Battery - per
UPM)
Battery
(Positive, Negative, Ground)
7
4
1
NOTE 1
V
Because of the future upgradability to a fully rated 400V/380V 825 kVA UPS with the addition of the FI-UPM, these conduit sizes are
specified for an 825 kVA UPS.
NOTE 2
V
Bypass conduit data is not applicable to IOM configurations.
Battery Conductor Routing
NOTE
For the 9395P-900 400/415/380V models, the max output is 825 kW/ 825 kVA.
Table 3-24. 400V/380V Power Cable Conduit Requirements (Continued)
UPS Model
Voltage
Terminal
Number of
Wires in Conduit
Minimum Conduit
Trade Size
Number of
Conduits
Table 3-25. Recommended Input Circuit Breaker Ratings (100% and 80% Load Rating)
UPS Model
Input Rating
%
480V
415V
400V
380V
Eaton 9395P-900/900
100
1600A
N/A
N/A
N/A
80
2000A
N/A
N/A
N/A
Eaton 9395P-900/825
100
1600A
1600A
1600A
1600A
80
1600A
2000A
2000A
2000A
Eaton 9395P-1200/750
100
1200A
1600A
1600A
1600A
80
1600A
2000A
2000A
2000A
Eaton 9395P-1200/675
100
1200A
1200A
1200A
1200A
80
1600A
1600A
1600A
1600A
Eaton 9395P-1200/600
100
1000A
1200A
1200A
1200A
80
1200A
1600A
1600A
1600A
Eaton 9395P-900/550
100
1000A
1000A
1000A
1000A
80
1200A
1200A
1200A
1200A
Eaton 9395P-900/500
100
800A
1000A
1000A
1000A
80
1000A
1200A
1200A
1200A
Eaton 9395P-900/450
100
700A
800A
800A
800A
80
1000A
1000A
1000A