Table 3-1: FI-UPM Cabinet Weight
The FI-UPM cabinet uses forced air cooling to regulate internal component temperature. Air inlets are
in the front of the cabinet and outlets are in the top. Allow clearance in front of and above each cabinet
for proper air circulation. The clearances required around the FI-UPM cabinet are shown in Table 3-2.
.
Table 3-2: FI-UPM Cabinet Clearances
The basic environmental requirements for operation of the FI-UPM are:
•
Ambient Temperature Range: 0–40°C
•
Recommended Operating Range: 20–25°C
•
Maximum Relative Humidity: 95%, noncondensing
The FI-UPM ventilation requirements are shown in Table 3-3.
.
Table 3-3: FI-UPM Air Conditioning or Ventilation Requirements During Full Load Operation
Ventilation required for cooling air exhaust: approximately 920 liter/sec/250/300kVA unit, +260 liter/sec
(ISBM).
Model
Weight
kg)
Shipping
Installed
Eaton 9395P FI-UPM
690
650
From Top of Cabinet
450 mm minimum clearance for ventilation
From Front of Cabinet
900 mm working space
From Back of Cabinet
None Required
From Right Side of Cabinet
None Required
From Left Side of Cabinet
None Required
Rating
Heat Rejection
kW
Heat rejection
BTU / h x 1000
250 kVA
10.1
34.5
300 kVA
12.5
42.7
Summary of Contents for Power Xpert 9395P
Page 1: ...Mechanical Installation Manual Power Xpert 9395P Field Installed UPM P 16400478...
Page 2: ......
Page 3: ...Power Xpert 9395P Field Installed UPM Mechanical Installation Manual...
Page 6: ......
Page 8: ......
Page 14: ...6...
Page 21: ...Figure 3 7 Eaton 9395P FI UPM Cabinet as Shipped on Pallet...
Page 22: ......
Page 28: ......
Page 30: ...Notes...