NOTE
A flat cabinet joining bracket is provided for securing the cabinets at the top front (see Step 7).
6.
Remove and retain one top screw and two bottom screws securing the FI-UPM front panel (see
Figure 4-2). Lift the panel straight up to remove it from the panel hanger bracket at the top of the
cabinet.
7.
Locate the small flat bracket and screws from the hardware kit. Align the holes in the small flat
bracket over holes in the top of the FI-UPM and UPS cabinets. Secure the bracket with the screws
from the hardware kit.
8.
Reinstall the FI-UPM front panel removed in Step 6, and secure with the retained hardware.
9.
If permanently mounting the system, proceed to Step 10; otherwise, continue to Step 12.
10. Using the retained hardware, reinstall the left shipping bracket removed in Section 4.2, Step 2 on
page 16 to the left side of the FI-UPM cabinet with the angle facing outward (see Figure 4-1 on
page 16).
11. Secure the cabinet to the floor with customer-supplied hardware.
12. Proceed to Section 4.4.
Figure 4-3. UPS Cabinet Wire Entry Plate and Knockout Locations (Left side view)
1
Wire entry knockout. Remove knockout to route wires between cabinets. (Install nylon-
grommet after removal of knockout.)
2
Wire Entry Plate Remove plate to route wires between cabinets.
1
2
Summary of Contents for Power Xpert 9395P
Page 1: ...Mechanical Installation Manual Power Xpert 9395P Field Installed UPM P 16400478...
Page 2: ......
Page 3: ...Power Xpert 9395P Field Installed UPM Mechanical Installation Manual...
Page 6: ......
Page 8: ......
Page 14: ...6...
Page 21: ...Figure 3 7 Eaton 9395P FI UPM Cabinet as Shipped on Pallet...
Page 22: ......
Page 28: ......
Page 30: ...Notes...