Configuring the Card
Eaton Power Xpert Gateway PXGX PDP Card User’s Guide 164202122—Rev 1
29
Management from an SNMP NMS
To access the PXGX PDP Card using SNMP:
1.
Verify that the NMS is configured for the correct community strings or SNMPv3 user names and
passwords, as shown on the SNMP Web page. See “Community Strings and Trap Recipients” on
page 27.
2.
Verify that the NMS is a Trusted Host, or that your PXGX PDP Card is configured for unrestricted SNMP
access on the Access Control Configuration Web page. See “Changing SNMP Access” on page 27.
3.
Select the
MIB Files
folder from the
Documentation
menu (or visit
www.eaton.com/powerxpert
) for
the following MIB files for the PXGX PDP Card:
4.
Add these files to the MIB database of your SNMP management software (such as HP OpenView
™
and
IBM
®
Systems Director).
5.
Use the facilities provided by the SNMP management software to access the individual MIB objects.
See Chapter 6, “MIB Files” on page 52 for more information.
Configuring Modbus TCP/IP Options
To limit access to the card from trusted Modbus Transmission Control Protocol/Internet Protocol (TCP/IP)
addresses only:
1.
Select
Access Control
from the Configuration menu.
2.
Select the
Modbus TCP access restricted by IP/hostname
check box.
3.
Type the trusted host's IP addresses or host names, separated by a semicolon, in the
Trusted IPs/
hostnames
field.
Note:
When using host names, verify that the IP address of your network DNS Server is configured
(see “Network Configuration” on page 21).
4.
Click
Apply
and then
OK
to save the settings.
For information on Modbus registers, see Chapter 7, “Modbus Registers” on page 55. See “Returning Error
Codes” on page 57 to change how error codes are returned.
MIB Name
Filename
Description
Eaton PDU MIB
EATON-PDU-MIB.txt
Meters available from the PDP, including identification,
input, output, configuration, tests, alarms, bypass, traps,
panel data, and circuit breaker data
Eaton EMP MIB
EATON-EMP-MIB.txt
Meters and settings for the EMP
Eaton Power Meter MIB
EATON-PWR-MIB.txt
Meters for:
l
Power quality
l
Real-time measures of voltage, currents, and power
l
Minimum, average, and maximum measures for voltage,
currents, frequency, and power factor
l
Energy measures and power demand
Eaton PowerChain Device MIB
EATON-PCD-MIB.txt
Provides commonly supported voltage, current, frequency,
and percent load measures, as well as digital inputs/outputs
and generic sensor readings for PowerChain devices.
Eaton Traps MIB
EATON-PXG-MIB.txt
Alarms and notifications (traps)
Eaton Object Identifier (OID)
assignments
EATON-OIDS.txt
Base document for all OID assignments for Eaton's MIBs
RFC 4133 Entity MIB
ENTITY-MIB.txt
Identification and description of each device attached to the
card
RFC 4268 Entity State MIB
ENTITY-STATE-MIB.txt
Five availability status meters for each device attached to
the card
RFC 4268 Entity State MIB Part 2
ENTITY-STATE-TC-MIB.txt
Possible state values for the Entity State MIB