39
9. Modbus register map
Power XPert® release triP unit for MagnuM PXr circuit breakers
MN013015EN January 2022 www.eaton.com
Table 21. Modbus real-time data status decoding.
Primary status
code register
number 6145
(high)
Definition
secondary
status code
register
number 6145
(low)
Definition
0x01
Open
0x03
Test mode
0x02
Closed
0x07
Powered-up
0x03
Tripped
0x08
Alarm
0x04
Alarmed
0x0D
Picked-up
cause of status register
number 6146
Definition
0x0000
Unknown
0x0001
Normal
0x0003
Instantaneous
0x0005
Instant. neutral over current
0x000E
Aux-power under power
0x001F
Operations count
0x0021
Control via communication
0x0029
Battery low alarm
0x003D
Long delay
0x003E
Short delay
0x0049
High load alarm 1
0x004B
Making current release
0x004C
Fixed hardware instantaneous
0x004D
Setpoints error
0x004E
Over temperature
0x0050
Long delay neutral over current
0x0054
Ground fault
0x0055
Earth fault
0x0071
Calibration
0x0088
Real-time clock
0x0099
MM mode
0x009A
Breaker mechanism fault
0x07FD
Non-volatile memory error
0x07FE
Watchdog fault
0x009E
Short delay neutral over current
0x009F
Thermal memory alarm
0x00A0
Local test from LCD
0x00A1
High load alarm 2
0x00A2
Ground fault pre-alarm