43
9. Modbus register map
Power XPert® release triP unit for MagnuM PXr circuit breakers
MN013015EN January 2022 www.eaton.com
9.4.2 Group 1 – protection group
Table 25. Modbus protection group data (continued).
func.
code
register
number
address
(hex)
setpoint name
r/w
Definition
6
3000
0x0BB7
Password
W
Factory default = 00000
3,4,6
3001
0x0BB8
Group 1 = protection
R/W
0x01FF selects group 0
3,4
3002
0x0BB9
Rating information
R
Values: 100, 200, 250, 300, 400, 500, 600, 630, 800, 1000, 1200, 1250, 1600,
2000, 2500, 3000, 3200, 4000, 5000, 6300
3,4
3003
0x0BBA
Breaker frame
R
0 = NRX NF
1 = NRX RF
2 = Magnum standard
3 = Magnum narrow
4 = Magnum double standard
5 = Magnum double narrow
3,4
3004
0x0BBB
Style
R
0 = PXR20VN30LNNC
1 = PXR20VN30LNNM
2 = PXR20VN30LGNC
3 = PXR20VN30LGNM
4 = PXR20VN30LGAC
5 = PXR20VN30LGAM
6 = PXR25VN30LNNM
7 = PXR25VN30LGNM
8 = PXR25VN30LNAM
9 = PXR25VN30LGAM
10 = PXR20VN30LNAM
11 = PXR20VN30LNAC
3,4,6
3006
0x0BBD
LD thermal memory
R/W
0 = disable
1 = enable
3,4,6
3007
0x0BBE
ZSI
R/W
0 = disable
1 = enable
3,4,6
3008
0x0BBF
LD slope
See
note
PXR 20 (read)
2 = I
2
t
PXR 25 (read/write)
0 = I
0.5
t
1 = It
2 = I
2
t
3 = I
4
t
3,4,6
3009
0x0BC0
LD pickup (Ir)
See
note
PXR 20 (read only)
40 = 0.4xI
n
50 = 0.5xI
n
60 = 0.6xI
n
70 = 0.7xI
n
75 = 0.75xIn
80 = 0.8xI
n
90 = 0.9xI
n
95 = 0.95xI
n
98 = 0.98xI
n
100 = 1.0xI
n
PXR 25 (read/write) valid range:
40 to 100
3,4,6
3010
0x0BC1
LD time (tr)
See
note
PXR 20 (read only)
5 = 0.5s
10 = 1s
20 = 2s
40 = 4s
70 = 7s
100 = 10s
120 = 12s
150 =15s
200 = 20s
240 = 24s
PXR 25 (read/write) valid range:
5 to 240
3,4,6
3011
0x0BC2
High load alarm 1
R/W
Value is percentage x I
r
Valid range: 50 to 115, must be < high load 2
3,4,6
3012
0x0BC3
SD slope
R/W
0 = flat
1 = I
2