47
10 Available protection settings
PXR tRiP units foR PoweR Defense molDeD case ciRcuit bReakeRs
MN012007EN March 2019 www.eaton.com
10.2.27 PDG4 PXR20 settings
frame
800 a
all
all
800 a
G styles
Profile
long delay
short delay
instantaneous
Ground
Dial
ir (a)
tr(s)@6x ir
isd (x lr)
tsd (s)
ii (x in)
ig (x in)
tg (s)
setting
Pickup ir
(amps)
time (s)
at 6x (ir)
Pickup (isd)
isd =nx (lr)
time (tsd)
tsd (s)
Pickup li = nx (in)
Pickup (ig)
lg = nx (in)
time (tg)
tg (s)
a
320
0.5
1.5
0.050
2
0.2
0.100
b
350
1
2.0
0.100
3
0.3
0.150
c
400
2
2.5
0.150
4
0.4
0.200
D
450
4
3.0
0.200
5
0.6
0.300
e
500
7
4.0
0.300
6
0.8
0.500
f
550
10
5.0
0.400
6.5
1.0
0.750
G
600
12
6.0
0.500
7
0.2
1.000
H
630
15
7.0
0.067
7.5
0.5
0.067
J
700
20
8.0
0.150
8
1.0
0.150
k
800
24
OFF
0.300
8.5
OFF
0.300
Flat
Instantaneous
override
Trip
Flat
I
2
t
6800 A
Alarm
I
2
t
Pickup (Isd) and (Ii) limited by Max Instantaneous
10.2.28 PDC4 PXR20 settings
frame
800 a
1000 a
all
all
800 a
1000 a
G styles
Profile
long delay
short delay
instantaneous
Ground
Dial
ir (a)
tr(s)@6x ir
isd (x lr)
tsd (s)
ii (x in)
ig (x in)
tg (s)
setting
Pickup ir (amps)
time (s)
at 6x (ir)
Pickup (isd)
isd =nx (lr)
time (tsd)
tsd (s)
Pickup li = nx (in)
Pickup (ig)
lg = nx (in)
time (tg)
tg (s)
a
320
400
0.5
1.5
0.050
2
2
0.2
0.100
b
400
550
1
2.0
0.100
3
3
0.3
0.150
c
450
630
2
2.5
0.150
4
4
0.4
0.200
D
500
700
4
3.0
0.200
5
5
0.6
0.300
e
550
750
7
4.0
0.300
6
6
0.8
0.500
f
600
800
10
5.0
0.400
6.5
6.5
1.0
0.750
G
630
850
12
6.0
0.500
7
7
0.2
1.000
H
700
900
15
7.0
0.067
7.5
7.5
0.5
0.067
J
750
950
20
8.0
0.150
8
8
1.0
0.150
k
800
1000
24
OFF
0.3
8.5
8.0
OFF
0.300
Flat
Instantaneous override
Trip
Flat
I
2
t
6800 A
8000 A
Alarm
I
2
t
Pickup (Isd) and (Ii) limited by Max Instantaneous