57
11 Modbus register map
PXR tRiP units foR PoweR Defense molDeD case ciRcuit bReakeRs
MN012007EN March 2019 www.eaton.com
Register
bit
field
mask
field
set point
name
R/w
format
Value definition
unit
Dec
HeX
403013
BC4
Language
R/W
Encoded
set language on local LCD display
0x01 --> English
0x02 --> German
0x03 --> French
0x04 --> Spanish
0x05 --> Italian
0x06 --> Chinese
0x07 --> Russian
0x08 --> Dutch
0x09 --> Danish
0x10 --> Greek
0x11 --> Portuguese
0x12 --> Swedish
0x13 --> Finnish
0x14 --> Czech
0x15 --> Estonian
0x16 --> Hungarian
0x17 --> Lithuanian
0x18 --> Latvian
0x19 --> Polish
0x20 --> Slovenian
0x21 --> Slovak
0x22 --> Bulgarian
0x23 --> Romanian
0x24 --> Croatian
403014
BC5
LCD_rotation
R/W
Encoded
Setting LCD display direction
0 <--> horizontal
1 <--> vertical - left
2 <--> vertical - right
403015
BC6
Relay_config1
R/W
Encoded
Relay 1/2/3 function configuration
403016
BC7
Relay_config2
R/W
Encoded
OFF_RELAY = 0x0000
403017
BC8
Relay_config3
R/W
Encoded
TRIP_OVERLOAD_RELAY = 0x0001
TRIP_NEUTRAL_RELAY = 0x0002
TRIP_SHORTCIRCUIT_RELAY = 0x0003
TRIP_SHORTDELAY_RELAY = 0x0004
TRIP_INST_RELAY = 0x0005
TRIP_GROUND_RELAY = 0x0006
TRIP_MM_RELAY = 0x0007
TRIP_ALL_RELAY = 0x0008
ALARM_HL_ALARM_RELAY = 0x0010
ALARM_HL_LOAD_RELAY = 0x0011
ALARM_HIGHTEMP_RELAY = 0x0012
ALARM_GROUND_RELAY = 0x0013
ALARM_THERMAL_RELAY = 0x0014
ALARM_WATCHDOG_RELAY = 0x0015
ALARM_LOW_BAT_RELAY = 0x0016
ALARM_INTERNAL_FAULT_RELAY = 0x0017
ALARM_STP_ERROR_RELAY = 0x0018
ALARM_BRK_HEALTH_RELAY = 0x0019
ALARM_COMM_FAULT_RELAY = 0x001A
ALARM_ALL_RELAY = 0x001B
AUX_RELAY = 0x0020
BELL_RELAY = 0x0021
MM_ACTIVE_RELAY = 0x0022
ZSI_ACTIVE_RELAY = 0x0023
ZSI_INPUT_RELAY = 0x0024
ZSI_OUTPUT_RELAT = 0x0025
COMM_OPEN_BREAKER_ PULSE_ RELAY = 0x0026
COMM_CLOSE_BREAKER_PULSE_RELAY = 0x0027
OUTPUT_RELAY = 0x0028
403018
BC9
Pole location -
phase a(1)
R/W
Encoded
Pole location - phase A(1)
0 - left
1 - right
403019
BCA
Reserved
403020
BCB
Reserved
403021
BCC
Reserved