11 Modbus register map
PXR tRiP units foR PoweR Defense molDeD case ciRcuit bReakeRs
MN012007EN March 2019 www.eaton.com
Remote Control Date Format
control
group
Definition
Password
Decimal byte
Decimal word
42903
42902
42901
42903
42902
42901
byte 5
byte 4
byte 3
byte 2
byte 1
byte 0
word 3
word 2
word 1
Reset
Reset trip
No
255
255
253
0
0
2
65535
64768
2
Reset min/max currents
Yes
255
254
242
0
1
13
65534
61952
269
Reset min/max line-to-
neutral voltages
Yes
255
254
240
0
1
15
65534
61440
271
Reset min/max line-to-line
voltages
Yes
255
254
241
0
1
14
65534
61696
270
Reset peak demand watts
Yes
255
255
251
0
0
4
65535
64256
4
Reset all min/max values
Yes
255
254
251
0
1
4
65534
64256
260
Reset energy
Yes
255
255
247
0
0
8
65535
63232
8
Reset trip count
Yes
255
250
254
0
5
1
65530
65024
1281
Reset operations count
Yes
255
254
253
0
1
2
65534
64768
258
Reset temperature
Yes
255
250
253
0
5
2
65530
64768
1282
Reset runtime
Yes
255
254
252
0
1
3
65534
64512
259
Reset all diagnostics
information
Yes
255
250
252
0
5
3
65530
64512
1283
Reset powered up
indication
No
255
255
252
0
0
3
65535
64512
3
Open breaker
Yes
254
255
255
1
0
0
65279
65281
0
Maintenance
Mode
Enable maintenance mode
No
254
255
247
1
0
8
65279
63233
8
Disable maintenance mode No
254
255
246
1
0
9
65279
62977
9
Relay Output
Activate relay output 1
No
251
254
254
4
1
1
64510
65028
257
De-activate relay output 1
No
251
253
254
4
2
1
64509
65028
513
Activate relay output 2
No
251
254
253
4
1
2
64510
64772
258
De-activate relay output 2
No
251
253
253
4
2
2
64509
64772
514
Activate relay output 3
No
251
254
252
4
1
3
64510
64516
259
De-activate relay output 3
No
251
253
252
4
2
3
64509
64516
515