Product description
Power Xpert
®
UX with W-VACi circuit breaker 6063308 G01 01 14 July 2011 www.eaton.com
23
2.4.2
Environmental conditions
During operation
Environment
In accordance with IEC 62271-1 par. 2.1.1,
Limit values below, among others, apply
Ambient temperature
Maximum over 24 hours
+40°C (adequate de-rating if higher ambient conditions apply)
Average over 24 hours
+35°C
Minimum
-5°C
Altitude at site
Maximum altitude
1000 m above sea level (adequate de-rating if higher altitude conditions
apply)
Humidity
Relative humidity
Maximum over 1 month
90%
Sound level produced
Average
< 70 dBA
During storage
Environment
In accordance with IEC 62271-1 par. 2.1.1
2.4.3
Dimensions and weights
Main dimensions (standard model)
Circuit-breaker panel
Depth
Width
(C)
Height
(A)
Height including arc
chamber (B)
12 kV and 17.5 kV
UX17 25 kA 630 A 600 mm wide
1310 mm
600 mm
2200 mm
2760 mm
UX17 31.5 kA 1250 A 600 mm wide
1310 mm
600 mm
2200 mm
2760 mm
UX17 40 kA 2000 A 800 mm wide*
1325 mm
800 mm
2200 mm
2760 mm
UX17 40/50 kA 2000 A 800 mm wide
1500 mm
800 mm
2200 mm
2760 mm
UX17 40/50 kA 3150 A 1000 mm wide
1500 mm
1000 mm
2200 mm
2760 mm
24 kV
UX24 20 kA 800 A 800 mm wide
1570 mm
800 mm
2320 mm
2880 mm
UX24 25 kA 1250 A 800 mm wide
1570 mm
800 mm
2320 mm
2880 mm
UX24 25 kA 2000 A 1000 mm wide
1570 mm
1000 mm
2320 mm
2880 mm
UX24 25 kA 2500 A 1000 mm wide
1570 mm
1000 mm
2320 mm
2880 mm
*: IAC of this panel is 26.3 kA-1s