System assembly
Power Xpert
®
UX with W-VACi circuit breaker 6063308 G01 01 14 July 2011 www.eaton.com
37
3.5.3
Connecting the auxiliary cables
Proceed as follows:
1. Remove the cover from the cable duct (see arrow in
illustration).
2. Feed the auxiliary cables into the switch panel from
underneath.
3. Secure the cables in the cable duct with cable clips or
tie-wraps.
4. Connect the cables in accordance with the diagram
pack.
5. Refit the cable duct cover.
Fig. 3-12 Connecting auxiliary cable
3.5.4
Inter-panel connection of auxiliary
cables
Auxiliary cables for inter-panel connection may come to
the adjacent panel through the round or rectangular holes,
covered with grommets, in the side sheet of LV
compartment. Alternatively they may exit the LV
compartment at the top, run along the switchgear in the
LV Cable way (see arrow) and enter the adjacent or other
panels in the switchgear in the same way.
Fig. 3-13 Inter-panel connection of auxiliary cables