System operation
Power Xpert
®
UX with W-VACi circuit breaker 6063308 G01 01 14 July 2011 www.eaton.com
39
4.1.1
Mechanical operation door open
When the door is open the circuit breaker or contactor
withdrawable unit can be operated directly from the
controls mounted on the front of the unit. For full
information refer to the individual operations and
maintenance manual.
If the control plug is connected then a full functional test of
the unit is possible.
NOTE
The door cannot be opened when the unit is in the
Service position. To open the door make sure the
unit is in the OFF position and it is racked out fully to
the TEST position. This will release the door
interlock mechanism and the door can now be
opened.
NOTE
Door Interlock Defeat Mechanism: To open the door
in an emergency, remove two screws.
4.1.2
Charging the closing spring
For operating of the circuit breaker unit see the user
manual of the W-VAC
i
.
1. Secondary Connector
2. Manual Close Button
3. Closed/Open Indicator
4. Manual Open Button
5. Front Panel
6. Manual Charging Handle
7. Nameplate
8. Spring Charged/Discharged Indicator
9. Operation Counter
Fig. 4-1 Door Interlock defeat operation
Fig. 4-2 Circuit Breaker
1
2
3
4
5
6
7
8
9