INSTALLATION REFERENCE
EATON
Powerware
®
225 kVA PDU Installation and Operation Manual
S
164201629 Rev D
www.powerware.com
A−5
Table E. PDU Cooling Requirements During Full Load Operation with 600V Transformer
Rating
Voltage
Heat Rejection
kVA
K−factor
Input
Output
Watts
BTU/hr
Kg−cal/hr
30
1
600
208/120
1555
5308
104
30
13
600
208/120
1536
5243
102
30
20
600
208/120
1382
4717
92
50
1
600
208/120
2592
8847
173
50
13
600
208/120
2560
8738
170
50
20
600
208/120
2304
7864
153
75
1
600
208/120
3888
13270
259
75
13
600
208/120
3564
12164
237
75
20
600
208/120
3456
11795
230
100
1
600
208/120
4752
16219
316
100
13
600
208/120
4320
14744
287
100
20
600
208/120
4158
14191
276
125
1
600
208/120
6534
22300
434
125
13
600
208/120
5616
19167
373
125
20
600
208/120
4212
14376
280
150
1
600
208/120
7128
24328
474
150
13
600
208/120
5508
18799
366
150
20
600
208/120
5184
17693
345
200
1
600
208/120
7830
26724
520
200
13
600
208/120
6426
21932
427
200
20
600
208/120
5994
20457
398
225
1
600
208/120
8910
30409
592
225
13
600
208/120
7236
24696
481
Summary of Contents for Powerware 225 kVA Three-Phase Power Distribution Unit