EATON
Powerware
®
225 kVA PDU Installation and Operation Manual
S
164201629 Rev D
www.powerware.com
4−1
Chapter 4
Installing a Remote Emergency Power−off Switch
A latching−type Remote Emergency Power−off (REPO) switch can be used in an
emergency to shut down the UPS and remove power to the critical load from a
location away from where the PDU is installed. Figure 4-1 shows an Eaton REPO
switch.
Contact Block (Back View, Faceplate Removed)
REPO Switch (Front View)
Figure 4-1. Eaton REPO Switch
NOTE
Before installing a REPO switch, verify that the PDU was installed according to the instructions in
Chapter 3, Installing the PDU."
NOTE
When installing the REPO switch, you must install conduit between the device and the PDU cabinet
for wiring the switch.
NOTE
The REPO switch must be a normally−open or normally−closed latching-type switch not tied into any
other circuits. The factory default configuration is set up for use with a normally−open switch. To use a
normally−closed switch, the configuration must be changed during setup by an Eaton Customer Service
Engineer
.
NOTE
This procedure is intended to be used for the installation of the Eaton REPO switch. If installing
another manufacturer’s switch, use this procedure only as a guide.
NOTE
The REPO switch wiring must be in accordance with NEC
®
Article 725 Class 2 requirements.
To install a REPO station:
1.
Verify the PDU is turned off and all power sources are removed. See Chapter 6,
PDU Operating Instructions," for shutdown instructions.
2.
Securely mount the REPO station. Recommended locations include operator’s
consoles or near exit doors. See Figure A-42 on page A−56 for enclosure
dimensions and wiring knockouts.
3.
If not already open, unfasten the front door latch and swing the doors open.
4.
Loosen the screws securing the inside distribution panel doors and swing the
doors open.
Figure 4Table 4