INSTALLATION REFERENCE
EATON
Powerware
®
225 kVA PDU Installation and Operation Manual
S
164201629 Rev D
www.powerware.com
A−37
Table M. Powerware 225 kVA PDU Input Power Cable Terminations (600V)
Terminal Function
Rating
(kVA)
Main Breaker
Rating
Terminal
Function
Size of Pressure
Termination
Tightening Torque
Nm (lb in)
Type and Size
Screw
AC Input to Main
Breaker CB1
30
50A
A
Phase A
1 – #8
8 (75)
Slotted
B
Phase B
1 – #8
8 (75)
Slotted
C
Phase C
1 – #8
8 (75)
Slotted
N
Neutral
Not required
50
60A
A
Phase A
1 – #6
8 (75)
Slotted
B
Phase B
1 – #6
8 (75)
Slotted
C
Phase C
1 – #6
8 (75)
Slotted
N
Neutral
Not required
75
100A
A
Phase A
1 – #3
8 (75)
Slotted
B
Phase B
1 – #3
8 (75)
Slotted
C
Phase C
1 – #3
8 (75)
Slotted
N
Neutral
Not required
100
125A
A
Phase A
1 – #1
13.5 (120)
3/16
"
Hex
B
Phase B
1 – #1
13.5 (120)
3/16
"
Hex
C
Phase C
1 – #1
13.5 (120)
3/16
"
Hex
N
Neutral
Not required
125
150A
A
Phase A
1 – 1/0
13.5 (120)
3/16
"
Hex
B
Phase B
1 – 1/0
13.5 (120)
3/16
"
Hex
C
Phase C
1 – 1/0
13.5 (120)
3/16
"
Hex
N
Neutral
Not required
150
200A
A
Phase A
1 – 3/0
13.5 (120)
3/16
"
Hex
B
Phase B
1 – 3/0
13.5 (120)
3/16
"
Hex
C
Phase C
1 – 3/0
13.5 (120)
3/16
"
Hex
N
Neutral
Not required
200
250A
A
Phase A
2 – 1/0
31 (275)
5/16
"
Hex
B
Phase B
2 – 1/0
31 (275)
5/16
"
Hex
C
Phase C
2 – 1/0
31 (275)
5/16
"
Hex
N
Neutral
Not required
225
300A
A
Phase A
2 – 1/0
31 (275)
5/16
"
Hex
B
Phase B
2 – 1/0
31 (275)
5/16
"
Hex
C
Phase C
2 – 1/0
31 (275)
5/16
"
Hex
N
Neutral
Not required
Customer Ground
All
All
G
Ground
1 – 1/0
31 (275)
5/16
"
Hex
Summary of Contents for Powerware 225 kVA Three-Phase Power Distribution...
Page 141: ......
Page 142: ...164201629D 164201629 D...