A−57
A.8
Optional Floorstand
A floorstand can be used to support the PDU when installed in facilities with raised
floors that will not support the weight of the PDU directly (see Figure A-43).
1.
Bolt the floorstand to the floor below the raised floor with customer−supplied
hardware.
2.
Adjust and level the floorstand to the height of the raised floor.
3.
Roll the PDU onto the floorstand from the front of the stand.
4.
Use the PDU leveling feet to secure the PDU on the floorstand.