COMMUNICATION
EATON
Powerware
®
225 kVA PDU Installation and Operation Manual
S
164201629 Rev D
www.powerware.com
7−2
S
Remote and local ability to clear call out alarms and events
S
Error detection and correction for misconfigured and disconnected modems
Remote Notification provides the option of receiving alarms and notices at a remote
location. Using the Terminal mode, the user calls the PDU to perform basic
monitoring. In the event of a PDU alarm or notice, the user is notified at the remote
location. The PDU calls through the modem to the user’s computer or pager and
leaves a message.
Remote Notification is an extension of the terminal mode with the additional support
algorithms necessary to control an external modem. Connection to the PDU is made
when a user calls the PDU on the phone. The user has exactly the same capabilities
as if using a terminal connected directly to an RS−232 port.
Remote Notification differs from the basic Terminal mode with the addition of the
following functions:
S
Call Answer
The Call Answer function allows the user to call into the PDU from a remote
location and enter terminal mode.
S
Call Out
The Call Out function allows the PDU to be configured to call either a remote
computer or numeric paging service over the phone line. Call Out allows the PDU
to call a remote computer and leave a one-line descriptive message of the alarm or
notice condition. Numeric paging support allows the PDU to call a paging service
and send numeric messages.
S
Housekeeping
The Housekeeping function maintains the link between the PDU and modem.
7.3
Terminal Mode
NOTE
The brackets ([ ]) in the following bullets indicate standard keyboard characters. To use a key
combination, hold down the Escape key and press the indicated letter key.
Terminal mode requires a computer with a serial (RS−232) port connected to the
RS−232 port on the PDU. The computer can use HyperTerminal set to emulate ANSI.
In Terminal mode, the following can be requested:
S
[ESC] [V]
displays the screens as shown on the PDU LCD.
S
[ESC] [P]
displays the Profile Log.
S
[ESC] [H]
displays the History Log.
S
[ESC] [A]
displays any new event.
7.3.1
PDU LCD Screens
To display the PDU LCD screens on a local computer, press
[ESC] [V]
. In this mode,
keyboard keys 1, 2, 3, 4, and 5 are substituted for the five pushbuttons on the PDU
LCD screen. The various screens are invoked using the same procedure described in
Chapter 6, PDU Operating Instructions.