EATON
Powerware
®
225 kVA PDU Installation and Operation Manual
S
164201629 Rev D
www.powerware.com
9−1
Chapter 9
Product Specifications
9.1
Model Number
The Power Distribution Unit (PDU) is housed in a free-standing cabinet with safety
shields behind the doors.
Model
Power Rating
Frequency
Powerware 225 kVA Three−Phase Power
Distribution Unit
30 to 225 kVA
60 Hz
9.2
PDU Input
Operating Input Voltage
(N10/–15%)
208 Vac nominal (60 Hz)
480 Vac nominal (60 Hz)
600 Vac nominal (60 Hz)
Operating Input Frequency
Range
5 Hz
Operating Input Current
See Appendix A, Table G, Table H, or Table I
9.3
PDU Output
Operating Output Voltage
(N10/–15%)
208 Vac nominal (60 Hz)
Operating Output Frequency
Range
5 Hz
Output Current
See Appendix A, Table G, Table H, or Table I
9.4
Environmental Specifications
Operating Temperature
0 to 40°C (32 to 104°F) without derating. The recommended operating
temperature is 25°C (77°F).
Operating Altitude
Maximum 1500m (5000 ft) at 40°C without derating
Storage Temperature
−40 to +60°C
Relative Humidity (operating
and storage)
10% to 95% maximum noncondensing
Acoustical Noise
Meets or exceeds ANSI C89 standard for transformers
EMI Suppression
Meets FCC Regulation 47, Part 15, for class A devices
Electrostatic Discharge (ESD)
Immunity
Meets IEC 801-2 specifications. Withstands up to 25 kV pulse without
damage and with no disturbance or adverse effect to the critical load.
Figure 9Table 9
Summary of Contents for Powerware 225 kVA Three-Phase Power Distribution...
Page 141: ......
Page 142: ...164201629D 164201629 D...