INSTALLATION REFERENCE
EATON
Powerware
®
225 kVA PDU Installation and Operation Manual
S
164201629 Rev D
www.powerware.com
A−34
15.
See Table J for PDU input circuit breaker ratings.
Table J. PDU Input Circuit Breaker Ratings
Input Voltage
kVA Rating
FLA
Main Breaker
Size
kAIC Rating
Standard
High
208
30
84
125A
65
100
50
139
175A
65
100
75
209
300A
65
100
100
278
350A
65
100
125
347
450A
65
100
150
417
600A
65
100
480
30
36
60A
35
65
50
60
80A
35
65
75
90
125A
35
65
100
120
150A
35
65
125
150
200A
35
65
150
180
225A
35
65
200
241
300A
35
65
225
271
350A
35
65
600
30
29
50A
18
25
50
48
60A
18
25
75
72
100A
18
25
100
96
125A
18
25
125
120
150A
18
25
150
144
200A
18
25
200
192
250A
25
35
225
241
300A
25
35
Summary of Contents for Powerware 225 kVA Three-Phase Power Distribution...
Page 141: ......
Page 142: ...164201629D 164201629 D...