SPECIFICATIONS
EATON
Powerware
®
5130 Rack/Tower UPS (1250–3000 VA) User’s Guide
S
164201730 Rev 2
www.powerware.com
55
Table 16. Battery Runtimes
Half Load
UPS Internal Batteries
+1 EBM
+2 EBMs
+3 EBMs
+4 EBMs
1250 VA/575W
15 min 22 sec
58 min
1 hr 40 min
2 hr 23 min
3 hr 5 min
1750 VA/800W
9 min 35 sec
36 min 11 sec
1 hr 2 min
1 hr 29 min
1 hr 55 min
2500 VA/1125W
11 min 15 sec
55 min
1 hr 40 min
2 hr 30 min
3 hr 26 min
3000 VA/2700W
10 min 15 sec
44 min
1 hr 13 min
1 hr 41 min
2 hr 10 min
Full Load
UPS Internal Batteries
+1 EBM
+2 EBMs
+3 EBMs
+4 EBMs
1250 VA/1150W
5 min
29 min 49 sec
54 min 38 sec
1 hr 19 min
1 hr 44 min
1750 VA/1600W
3 min 30 sec
16 min
28 min 30 sec
41 min
53 min 30 sec
2500 VA/2250W
3 min
23 min
42 min
1 hr 3 min
1 hr 25 min
3000 VA/2700W
3 min
17 min
32 min
47 min
1 hr 2 min
NOTE Battery times are approximate and vary depending on the load configuration and battery charge.