Eaton 5130 Rack/Tower UPS (1000–3000 VA) User's Guide
S
164201730 Rev 4
www.eaton.com/powerquality
53
Chapter 7
Specifications
Filter
Transformer
“AVR”
Charger
Inverter
Battery
Figure 30. Block Diagram
Table 10. Low-Voltage Model Specifications
Model Number
Power Levels
(Rated at
Nominal Inputs)
AC Input
Output on Battery Power
Nominal
Voltage
Voltage
Range
1
Frequency
Range
2
Voltage
3
Frequency
PW5130L1000-XL2U
1000 VA, 1000W
120V
89–151V
47–70 Hz (50 Hz
system),
56.5–70 Hz (60 Hz
system)
120V
(+6/-10%)
50/60 Hz
±
0.1%
PW5130L1500-XL2U
1500 VA, 1400W
PW5130L2200-XL2U
2200 VA, 1920W
PW5130L3000-XL2U
2880 VA, 2700W
PW5130L3000-XL3U
1
The high and low thresholds can be adjusted using the UPS Configuration tool (see page 43).
2
Up to 40 Hz in low-sensitivity mode (programmable using the UPS Configuration tool).
3
Adjustable to 100V (10% derating of output power) 120/127V.