SPECIFICATIONS
Eaton 5130 Rack/Tower UPS (1000–3000 VA) User's Guide
S
164201730 Rev 4
www.eaton.com/powerquality
54
Table 11. High-Voltage Model Specifications
Model Number
Power Levels
(Rated at
Nominal Inputs)
AC Input
Output on Battery Power
Nominal
Voltage
Voltage
Range
1
Frequency
Range
2
Voltage
3
Frequency
PW5130i1250-XL2U
1250 VA, 1150W
220–240V
160–294V
47–70 Hz (50 Hz
system),
56.5–70 Hz (60 Hz
system)
230V
(+6/-10%)
50/60 Hz
±
0.1%
PW5130i1750-XL2U
1750 VA, 1600W
PW5130i2500-XL2U
2500 VA, 2250W
PW5130i3000-XL2U
3000 VA, 2700W
PW5130i3000-XL3U
PW5130G3000-XL2U
3000 VA, 2700W
208V
160–263V
208V
(+6/-10%)
1
The high and low thresholds can be adjusted using the UPS Configuration tool (see page 43).
2
Up to 40 Hz in low-sensitivity mode (programmable using the UPS Configuration tool).
3
Adjustable to 100V (10% derating of output power) 120/127V.
Table 12. Weights and Dimensions
Low-Voltage Model Number
Dimensions (WxHxD)
Weight
PW5130L1000-XL2U
440
86
509 mm
17.3
”
3.4
”
20.0
”
24.6 kg (54.3 lb)
PW5130L1500-XL2U
26.3 kg (58.0 lb)
PW5130L2200-XL2U
440
86
634 mm
17.3
”
3.4
”
25.0
”
34.7 kg (76.4 lb)
PW5130L3000-XL2U
35.3 kg (77.9 lb)
PW5130L3000-XL3U
440
131
484 mm
17.3
”
5.2
”
19.0
”
33.8 kg (75.5 lb)
High-Voltage Model Number
Dimensions (WxHxD)
Weight
PW5130i1250-XL2U
440
86
509 mm
17.3
”
3.4
”
20.0
”
24.3 kg (53.6 lb)
PW5130i1750-XL2U
PW5130i2500-XL2U
440
86
634 mm
17.3
”
3.4
”
25.0
”
33.8 kg (74.5 lb)
PW5130i3000-XL2U
PW5130G3000-XL2U
440
86
634 mm
17.3
”
3.4
”
25.0
”
35.3 kg (77.9 lb)
PW5130i3000-XL3U
440
131
484 mm
17.3
”
5.2
”
19.0
”
34.3 kg (75.6 lb)