SPECIFICATIONS
Eaton 5130 Rack/Tower UPS (1000–3000 VA) User's Guide
S
164201730 Rev 4
www.eaton.com/powerquality
59
Table 16. Battery Runtimes (in minutes)
+4 EBMs
+3 EBMs
+2 EBMs
+1 EBM
UPS Internal Batteries
Load
PW5130i2500-XL2U (with PW5130N3000-EBM2U)
250 VA/225W
77
300
410
780
1064
625 VA/563W
28
122
207
309
412
1250 VA/1125W
11
55
100
150
206
2153 VA/1938W
6
31
59
90
120
2500 VA/2250W
3
23
42
63
85
PW5130i3000-XL2U / PW5130i3000-XL3U (with PW5130N3000-EBM2U or PW5130N3000-EBM3U depending on UPS
height)
300 VA/210W
80
270
500
705
901
750 VA/525W
39
143
308
370
482
1500 VA/1050W
16
62
117
160
210
2250 VA/1575W
8
35
59
85
105
3000 VA/2100W
5
24
40
59
89
3000 VA/2700W
3
17
32
47
62
NOTE
Battery times are approximate and vary depending on the load configuration and battery charge.