11
Table 1. Configuration Mode Parameters (cont.)
Parameter
LCD Message
Description
Default Settings
Manual Battery Test
Manual Bat Test
To initiate a manual battery test, press the
↵
↵
button Battery
Test
twice when “Manual Battery Test” is displayed on the
LCD. During the test the LCD displays ON BATTERY.
The UPS resets the automatic timer after a manual
battery test. The LCD displays “Battery not charged”
when UPS test is requested but the battery is not
fully charged.
Manual UPS Test
Manual UPS Test
To initiate a manual UPS self-test, press the
↵
↵
button
UPS Test
twice. During the test, the LCD displays ON BATTERY.
Site Wiring Fault Alarm
Site Fault Set
Select Enable or Disable. When enabled, the alarm sounds Detect Enable
when the ground connection is missing or the line and
neutral wires are reversed in the wall outlet.
Modem Support
Modem Support
This parameter is reserved for future use, and should not
No Modem Support
be modified by the user.
Number of Extended
Bat Pack Num Set
Select the number of EBMs connected to the UPS:
Extern Pack: 0
Battery Modules
• For 700-1500 VA models, select 0 through 2
• For 2000-3000 VA models, select 0 through 5.
You are prompted to save this setting. Refer to the
documentation that came with your battery pack for
more information.
Communications Lock-
COM Control
For greater levels of security, users may choose to have
Enable
out
Cmds
the UPS disregard shutdown commands that come from
the power management software or other communication
sources.
• When disabled, the UPS does not accept a shut down
command via the communication port, USB port, or
communication slot adapter.
• When enabled, the UPS operates normally in response
to external commands.
You are prompted to save this setting.
Load Segment Control
Load Group Set
Allows manual control of load segments (see “Load
Group 1On 2On
Segments” Section 5.3)
By repeatedly pressing the scroll button, the individual
load segments can be turned on and off.
CAUTION To prevent the unintentional shutdown of
specific load segments, confirm your selection before
pressing the
↵
↵
button.
Manual Bypass
Manual Bypass
This parameter is used to manually place the UPS in
Bypass OFF
GO
Bypass mode.
Configuration Mode
Config Mode Set
This parameter is reserved for future use, and should not
EscapeConfigMode
Setting
be modified by the user. The setting may be toggled
between EscapeConfigMode and Enter ConfigMode. 5.0
It should always be set to EscapeConfigMode.